Manual 37139C
UMT 1 - Measuring Transducer
© Woodward
Page 53/62
Appendix F.
List of Parameters
Product number
P/N _____________________________ Rev _______________________________
Version
UMT 1 _______________________________________________________________
Project
_____________________________________________________________________
Serial number
S/N _______________
Date
______________________________
Option
Parameter
Setting range
100/400/690 V
Default setting
Customer setting
BASIC DATA
Software version
-
-
SPRACHE/LANGUAGE
German/English
German
G
E
G
E
Coding
ON/OFF
OFF
1
0
1
0
Enter code
number
0000 to 9999
-
Password
Protection
ON/OFF
ON
1
0
1
0
Define level 1
code
0000 to 9999
0001
Define level 2
code
0000 to 9999
0002
Direct para.
YES/NO
NO
Y
N
Y
N
MEASUREMENT
Volt. transformer
secondary
50 to 125 / 50 to 480 V
100/400 V
Volt. transformer
primary
00.100 to 65.000 kV
00.400 kV
Current transf.
1 to 9999/1 A
1 to 9999/5 A
1000/1 A
1000/5 A
Connection type
1W / 1W4 / 1W3 / 2W3 / 2W4
2W4
Voltage transd.
secondary
50 to 120 / 50 to 480 V
100/400 V
Gen voltage
primary
0.10 to 650.00 kV
0.40 kV
Current transd.
10 to 9,990/1 A
10 to 9,990/5 A
1,000/1 A
1,000/5 A
Measurement
1W / 1W4 / 1W3 / 2W3 / 2W4
2W4
Pulse output
P.duration
0.04 to 1.00 s
0.10 s
Pulse output
+kWh / -kWh / +kvarh / -kvarh
+kWh
Pulse/kvarh
Logic
positive/negative
negative
p
n
p
n
Reactive energy
Pulse/kvah
0.1 to 150.00
1.0
Pulse/kWh
Logic
positive/negative
negative
p
n
p
n
Active energy
Pulse/kWh
0.1 to 150.00
1.0
Display kWh +-
on?
YES/NO
YY
Display kvarh +-
on?
YES/NO
YY
RESET kWh/kvarh
ON/OFF
OFF
1
0
1
0
Refresh time
Display
1 to 5 s
Measuring filter
Voltage
OFF / 0.04 to 2.56 s
Measuring filter
Current
OFF / 0.04 to 2.56 s
Measuring filter
Power
OFF / 0.04 to 2.56 s
Measuring filter
Frequency
OFF / 0.04 to 2.56 s