Manual 37139C
UMT 1 - Measuring Transducer
© Woodward
Page 23/62
Chapter 6.
Configuration
Configuration can be done via the front panel push buttons and the front panel LC display.
CAUTION
Please note that configuration only should be done while the system is not in operation.
NOTE
A list of all parameters may be found in Appendix F of this manual.
You can advance through the individual parameter screens if you are in configuration mode (simultaneously
pressing of "Digit
↑
" and "Cursor
→
" push buttons permits access to the configuration mode) by using the "Select"
button. If you press and hold the "Select" push button, the scroll function will be activated, allowing for the para-
meter screens to be advanced through more rapidly. The control unit will permit the operator to reverse up to four
previous screens (exception: it is not possible to reverse from the first parameter to the last parameter or to back-
up through the service screens). To perform the reverse function through the parameter screens, the "Select" and
"Cursor
→
" push buttons must be pressed and released simultaneously. The control unit will revert to automatic
mode if an entry isn’t performed, a change made, or any other action performed for 120 seconds.
NOTE
There are three different hardware versions described in this operating manual: A 100 V version [1], a
400 V version [4] and a 690 V version [7]. The versions vary as far as the configuration screens and the
parameter input ranges are concerned. The three types are differentiated by indicating the voltage: ([1]
..., [4] ... or [7] ...).
Adjust Settings:
SELECT (ANWAHL)
Configuration mode
Button "Select"
After the configuration mode is enabled, the subsequent screens can be viewed and
modified within the preset limits. Please note, that by depressing the "Select" but-
ton, the following screens are advanced by one screen each. If a parameter is confi-
gured "OFF", the related screens are not displayed or monitored by the control.
Pressing the "Select" button will advance the displayed screen to the next parame-
ter.