Manual 37139C
UMT 1 - Measuring Transducer
Page 34/62
© Woodward
Interface (
Option SU
)
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Screens for Protocol DK3964 (
Option SU
)
Data block
RK512 000
Data block RK512
0 to 255
Data block address in receiver (i.e. PLC).
Data word RK512
000
Data word RK512
0 to 255
Data word address in receiver (i.e. PLC).
Screens for Protocol Profibus DP Slave (
Option SU
)
Device number
Profibus 000
Device number profi-bus DP slave
0 to 126
Device number for the profi-bus DP slave.
Screens for Protocol Modbus RTU Slave (
Option SU
)
Device number
Modbus 000
Device number Modbus RTU Slave
1 to 255
Device number for the Modbus RTU Slave.
Baudrate
0000
Baudrate Modbus RTU Slave
1,200 / 2,400 / 4,800 / 9,600 / 19,200 Baud
The baud rate of the Modbus RTU Slave is defined here.
Parity
none
Parity Modbus RTU Slave
none / even / odd
The parity of the Modbus RTU Slave is defined here.
Stopbits
one
Stop bits Modbus RTU Slave
one / two
The number of stop bits of the Modbus RTU Slave is defined here.
Delay to send
Modbus 00.0ms
Waiting time transmission after read request
0.2 to 50.0 ms
After the read request by the master, the minimum waiting time before transmitting
the answer is the time previously set. This allows to adjust the time response to the
master so that it can process the answer.