Manual 37139C
UMT 1 - Measuring Transducer
Page 26/62
© Woodward
Password (Starting with Version 2.0xx / 3.0xx)
The unit is equipped with a three-level code and configuration hierarchy, which allows different user access to the
control. A distinction is made between:
Code level CS0
(User Level)
Factory password = none
This code level allows for monitoring of the system and does not permit access to the parameters. Configuration is
blocked.
Code level CS1
(Basis Service Level)
Factory password = "
0 0 0 1
"
This code level entitles the user to change selected parameters, like setting Bar/PSI, °C/°F, and clock adjustment.
Changing a password is not permitted at this level. This password expires two hours after entering the password
and the user is returned to the CS0 level.
Code level CS2
(Commissioning Level)
Factory password = "
0 0 0 2
"
Allows direct access to all parameters (displaying and changing). In addition, the user may also set the password
for levels CS1 and CS2. This password expires two hours after entering the password and the user is returned to
the CS0 level.
NOTE
Once the code level is entered, access to the configuration menus will be allowed for two hours or un-
til another password is entered into the control. If a user needs to exit a code level, then code level
CS0 should be entered. This will block any configuration of the control. A user may return to CS0 by al-
lowing the entered password to expire after two hours or by changing any one digit on the random
number generated on the password screen and entering it into the unit.
NOTE
(Starting with Version 2.1xx / 3.1xx)
The following configuration screen "enter code number" only appears if the parameter "pass-word
protection" is switched ON (see below).
Enter code
number 0000
Enter code number
0000 to 9999
Upon enabling the configuration mode, the user is required to enter an access code
number, which identifies the various users. The displayed number XXXX is a ran-
domly generated number (RN). If the random number is confirmed by pressing the
"Select" button without being changed, the current level of access maintained. Upon
entering either a level 1 or level 2 access code, the corresponding level of access is
granted. If an incorrect access code is entered the control unit changes to code level
0 and all access is blocked until a code level 1 or 2 access code is entered.
Password
Protection ON
Password protection
ON/OFF
ON
................ Password protection is enabled. Configuration access is enabled by
entering the appropriate password (Code level 1/2). If an incorrect
code number has been entered, configuration is blocked.
OFF
.............. Password protection is disabled. Access to configuration screens is
permanently set to code level 2 and the code number is not queried.
This parameter can only be changed if the code number of code lev-
el 2 has been entered.