AR-Protection Module – Automatic Reclosure [ANSI 79]
5.Startfct
Assignment
Start fct
-
[Protection Para
/<n>
/AR
/Start / FT]
5.n FT
Fast Trip after AR
attempt number.
Only available if a
start function was
assigned
0 - 6
0
[Protection Para
/<n>
/AR
/Start / FT]
5.t-FT
Trip delay for Fast
Trip
Only available if a
start function was
assigned
0 - 10.00s
0s
[Protection Para
/<n>
/AR
/Start / FT]
6.Startfct
Assignment
Start fct
-
[Protection Para
/<n>
/AR
/Start / FT]
6.FT
Fast Trip
Only available if a
start function was
assigned
inactive,
active
inactive
[Protection Para
/<n>
/AR
/Start / FT]
6.n FT
Fast Trip after AR
attempt number.
Only available if a
start function was
assigned
0 - 6
0
[Protection Para
/<n>
/AR
/Start / FT]
6.t-FT
Trip delay for Fast
Trip
Only available if a
start function was
assigned
0 - 10.00s
0s
[Protection Para
/<n>
/AR
/Start / FT]
Page 434
EN MRA4 04/09
Содержание SEG HighPROTEC MRA4
Страница 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Страница 3: ...Order Code EN MRA4 04 09 Page 3...
Страница 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Страница 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Страница 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...
Страница 486: ...Service Service General Within this menu you can initiate a reboot of the device Page 486 EN MRA4 04 09...