I-Protection Module – Overcurrent Protection [ANSI 50, 51, 67]
Commissioning: Overcurrent Protection, directional [ANSI 67]
Object to be tested
•
For each directional overcurrent element
II[1]...I[6]
are to be measured: the total tripping time
(recommendation) or alternatively tripping delays and the fallback ratios; each time 3 x single-phase
and 1 x three-phase.
Especially in Holmgreen connections, wiring errors can happen easily and
these are then detected safely. By measuring the total tripping time, it can
be ensured that the secondary wiring is o.k. (from the terminal on, up to the
trip coil of the CB ).
It is recommended to measure the total tripping time instead of the tripping
time. The tripping delay should be specified by the customer. The total
tripping time is measured at the position signaling contacts of the CBs (not
at the relay output!).
Total tripping time: = tripping delay (please refer to the tolerances of the
protection stages)
+ CB operating time (about 50 ms)
Please take the CB switching times from the technical data, specified in the
relevant documentation, provided by the CB manufacturer.
Necessary means
•
Synchronizable current and voltage sources
•
May be: ampere meters
•
Timer
Procedure
Synchronize the 3-phase current and voltage sources with each other. Then simulate the tripping directions to be
tested by the angle between current and voltage.
Testing the threshold values (3 x single-phase and 1 x three-phase)
Each time feed a current which is about 3-5% above the threshold value for activation/tripping. Check then the
threshold values.
Testing the total tripping delay
(recommendation)
Measure the total tripping times at the auxiliary contacts of the CB (CB tripping).
Testing the trip delay
(measured at the relay output)
Measure the tripping times at the relay output.
Testing the fallback ratio
Reduce the current to
97% below the trip value and check the fallback ratio.
Successful test result
The measured total tripping delays or individual tripping delays, threshold values and fallback ratios correspond
with those values, specified in the adjustment list. Permissible deviations/tolerances can be found under
Technical Data.
Page 286
EN MRA4 04/09
Содержание SEG HighPROTEC MRA4
Страница 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Страница 3: ...Order Code EN MRA4 04 09 Page 3...
Страница 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Страница 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Страница 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...
Страница 486: ...Service Service General Within this menu you can initiate a reboot of the device Page 486 EN MRA4 04 09...