V-Protection Module – Voltage Protection [ANSI 27/59]
Parameter
Description
Setting range
Default
Menu path
V(t)<8
Pick-up value
Only available if: Device
planning: V.Mode = V(t)<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t8
Tripping delay
Only available if: Device
planning: V.Mode = V(t)<
0.00 - 10.00s
3.00s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<9
Pick-up value
Only available if: Device
planning: V.Mode = V(t)<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t9
Tripping delay
Only available if: Device
planning: V.Mode = V(t)<
0.00 - 10.00s
3.00s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<10
Pick-up value
Only available if: Device
planning: V.Mode = V(t)<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t10
Tripping delay
Only available if: Device
planning: V.Mode = V(t)<
0.00 - 10.00s
3.00s
[Protection Para
/<n>
/V-Prot
/V[1]]
Page 358
EN MRA4 04/09
Содержание SEG HighPROTEC MRA4
Страница 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Страница 3: ...Order Code EN MRA4 04 09 Page 3...
Страница 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Страница 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Страница 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...
Страница 486: ...Service Service General Within this menu you can initiate a reboot of the device Page 486 EN MRA4 04 09...