Module: IEC60870-5-103
Global Protection Parameters of the IEC60870-5-103
Parameter
Description
Setting range
Default
Menu path
Slave ID
Device address (Slave ID)
within the bus system. Each
device address has to be
unique within a bus system.
1 - 247
1
[Device Para
/IEC 103]
t-call
If there is no request telegram
sent from Scada to the device
after expiry of this time - the
device concludes a
communication failure within
the Scada system.
1 - 3600s
60s
[Device Para
/IEC 103]
Transm priv meas
val
Transmit additional (private)
measuring values
inactive,
active
inactive
[Device Para
/IEC 103]
Baud rate
Baud rate
1200,
2400,
4800,
9600,
19200,
38400,
57600
19200
[Device Para
/IEC 103]
Physical Settings
Digit 1: Number of bits. Digit
2: E=even parity, O=odd
parity, N=no parity. Digit 3:
Number of stop bits. More
information on the parity: It is
possible that the last data bit
is followed by a parity bit
which is used for recognition
of communication errors. The
parity bit ensures that with
even parity ("EVEN") always
an even number of bits with
valence "1" or with odd parity
("ODD") an odd number of "1"
valence bits are transmitted.
But it is also possible to
transmit no parity bits (here
the setting is "Parity = None").
More information on the stop-
bits: The end of a data byte is
terminated by the stop-bits.
8E1,
8O1,
8N1,
8N2
8E1
[Device Para
/IEC 103]
Page 212
EN MRA4 04/09
Содержание SEG HighPROTEC MRA4
Страница 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Страница 3: ...Order Code EN MRA4 04 09 Page 3...
Страница 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Страница 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Страница 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...
Страница 486: ...Service Service General Within this menu you can initiate a reboot of the device Page 486 EN MRA4 04 09...