I-Protection Module – Overcurrent Protection [ANSI 50, 51, 67]
Parameter
Description
Setting range
Default
Menu path
nondir Trip at V=0
Only relevant for
current protection
modules/stages with
directional feature!
The device will trip
non directional if this
parameter is set to
active and no
direction could be
determined because
no reference voltage
(V=0) could be
measured any more
(e.g. if there is a
three-phase short
circuit close to the
device). If this
parameter is set to
inactive, the
protection stage will
be blocked in case
of V=0.
Only available if:
Device planning:
I.Mode = directional
inactive,
active
inactive
[Protection Para
/<n>
/I-Prot
/I[1]]
Page 282
EN MRA4 04/09