CLPU - Supervision Module Cold Load Pickup
Parameter set parameters of the Cold Load Pickup module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/CLPU]
ExBlo Fc
Activate (allow) or inactivate
(disallow) blocking of the
module/stage. This parameter is
only effective if a signal is
assigned to the corresponding
global protection parameter. If
the signal becomes true, those
modules/stages are blocked that
are parameterized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/CLPU]
Ex rev Interl Fc
Activate (allow) or inactivate
(disallow) blocking of the
module/stage. This parameter is
only effective if a signal is
assigned to the corresponding
global protection parameter. If
the signal becomes true, those
modules/stages are blocked that
are parameterized "Ex rev Interl
Fc = active".
inactive,
active
inactive
[Protection Para
/<n>
/CLPU]
t-Pickup Delay
If the Pickup Time (Delay) has
run out, a Cold Load Signal will
be issued.
0.00 - 300.00s
1.00s
[Protection Para
/<n>
/CLPU]
t-Release Delay
If the Release Time (Delay) has
run out, a Warm Load Signal will
be issued.
0.00 - 300.00s
1.00s
[Protection Para
/<n>
/CLPU]
I<
The CB is in the OFF Position, if
the measured current is less
than this parameter.
0.01 - 1.00In
0.01In
[Protection Para
/<n>
/CLPU]
EN MRA4 04/09
Page 343
Содержание SEG HighPROTEC MRA4
Страница 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Страница 3: ...Order Code EN MRA4 04 09 Page 3...
Страница 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Страница 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Страница 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...
Страница 486: ...Service Service General Within this menu you can initiate a reboot of the device Page 486 EN MRA4 04 09...