Field Parameters
CT sec
Nominal current of the
secondary side of the current
transformers.
1A,
5A
1A
[Field Para]
CT dir
Protection functions with
directional feature can only
work properly if the
connection of the current
transformers is free of wiring
errors. If all current
transformers are connected to
the device with a wrong
polarity, the wiring error can
be compensated by this
parameter. This parameter
turns the current vectors by
180 degrees.
0°,
180°
0°
[Field Para]
ECT pri
This parameter defines the
primary nominal current of the
connected earth current
transformer. If the earth
current is measured via the
Holmgreen connection, the
primary value of the phase
current transformer must be
entered here.
1 - 50000A
1000A
[Field Para]
ECT sec
This parameter defines the
secondary nominal current of
the connected earth current
transformer. If the earth
current is done via the
Holmgreen connection, the
primary value of the phase
current transformer must be
entered here.
1A,
5A
1A
[Field Para]
ECT dir
Earth fault protection with
directional feature depends
also on the correct wiring of
the earth current transformer.
A wrong polarity/wiring can be
corrected by means of the
settings "0°" or "180°". The
operator has the possibility of
turning the current vector by
180 degrees (change of sign)
without modification of the
wiring. This means, that – in
terms of figures - the
determined current indicator
was turned by 180° by the
device.
0°,
180°
0°
[Field Para]
Page 232
EN MRA4 04/09
Содержание SEG HighPROTEC MRA4
Страница 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Страница 3: ...Order Code EN MRA4 04 09 Page 3...
Страница 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Страница 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Страница 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...
Страница 486: ...Service Service General Within this menu you can initiate a reboot of the device Page 486 EN MRA4 04 09...