IG-Protection Module – Ground Fault [ANSI 50N/G, 51N/G, 67N/G]
IG-Protection Module – Ground Fault [ANSI 50N/G, 51N/G,
67N/G]
Available stages:
IG[1] ,IG[2] ,IG[3] ,IG[4]
If you are using inrush blockings the tripping delay of the earth current
protection functions must be at least 30ms or more in order to prevent
faulty trippings.
All earth current elements
IG[1]..IG[4]
are identically structured.
This module offfers Adaptive Parameter Sets.
Parameters can be modified within parameter sets dynamically by means of
Adaptive Parameter Sets.
Please refer to chapter Parameter / Adaptive Parameter Sets.
All
IG[1]...IG[4]
earth current protective elements can be planned user defined as non-directional or as
directional stages. This means, for instance, all 4 elements can be projected in forward/reverse direction. For
each element the following characteristics are available:
•
DEFT (UMZ)
•
NINV (AMZ)
•
VINV (AMZ)
•
LINV (AMZ)
•
EINV (AMZ)
•
MINV (AMZ)
•
VINV (AMZ)
•
EINV (AMZ)
•
Thermal Flat
•
IT
•
I2T
•
I4T
Explanation:
EN MRA4 04/09
Page 287
t = Tripping delay
t-char = Time multiplier/tripping characteristic factor
IG = Fault current
IG> = If the pick-up value is exceeded, the module/stage will be started.
Содержание SEG HighPROTEC MRA4
Страница 1: ...MRA4 HighPROTEC Feeder Protection Device Manual DOK HB MRA4E...
Страница 3: ...Order Code EN MRA4 04 09 Page 3...
Страница 59: ...Navigation Operation Navigation Operation EN MRA4 04 09 Page 59 1 4 2 3 5 7 6 8 9...
Страница 378: ...PQS Power Protection Module ANSI 32 37 Page 378 EN MRA4 04 09 P P Q P Q P Q Q Q P S S...
Страница 379: ...PQS Power Protection Module ANSI 32 37 EN MRA4 04 09 Page 379 Pr Q P Q P Qr...
Страница 486: ...Service Service General Within this menu you can initiate a reboot of the device Page 486 EN MRA4 04 09...