ENGLISH
52
Representation in
display:
The desired function must be activated in the pump,
see also chapter 4.3.
x
DP interface
for an integratable double-pump ma-
nagement with the functions:
x
Addition operation (optimum efficiency peak-load
operation)
x
Automatic fault-activated changeover
x
Duty/Standby mode:
x
Basic load pump swap after 24 hrs of accumulated
operating time
x
The terminals are locked.
9.1.2 Terminal assignment of the Stratos IF
modules and cable specification
(Figure 14)
x
Serial digital interface
PLR
for connecting to inter-
face converter or proprietary coupling modules:
Terminal cross-section: max. 2,5mm
2
Bus cable:
min. 2 x 0,34mm
2
, shielded,
(z.B. J-Y(ST)Y 2x2x0,8mm
2
)
Max. cable length:
500m
x
Serial digital interface
LON
for connecting to LON-
WORKS networks:
Terminal cross-section: max. 2.5 mm
2
Bus cable:
min. 2 x 0.34 mm
2
, drilled
(10 t/m), shielded
(e.g. J-Y(ST)Y 2x2x0.8 mm
2
)
Max. cable length:
-750 m for bus topology
with max. 3 m long stub ca-
bles
-500 m for free topology,
with max. 320 m between 2
intercommunicating nodes
The indicated cable lengths
are dependent on the used
cable typ.
x
Input for potential-free closed contact with the
function
Ext. Off
max. cable length: 100 m, 2-core cable, shielded
Terminal cross-section:
max. 1,5 mm
2
x
Input for potential-free closed contact with the
function
Ext. Min:
max. cable length: 100 m, 2-core cable, shielded
Terminal cross-section:
max. 1,5 mm
2
x
Output as potential-free opened contact with the
function
SBM:
max. cable length: 100 m, 2-core cable, not shiel-
ded
Terminal cross-section:
max. 1,5 mm
2
x
Control input
0...10V:
max. cable length: 25 m, 2-core cable, shielded
Terminal cross-section:
max. 1,5 mm
2
x
DP interface
max. cable length: 2.5 m, 2-core cable, not shielded
Terminal cross-section:
max. 1,5 mm
2
for the
Stratos IF modules
Ext.Min, Ext.Off, SBM
max. 2.5 mm
2
for the
Stratos IF modules
PLR, LON
9.2
Combination possibilities of the IF
modules for double-pump operation
Double pumps or two corresponding single pumps can
be retrofitted with a built-in double pump manage-
ment facility.
x
Stratos IF modules:
Two IF modules linked together
via the DP interface are required to allow the pumps
to communicate with each other. In addition to dou-
ble-pump management, the IF modules provide ot-
her interfaces for the double pump, see also chapter
9.1.1.
x
Conditions: A double pump or two corresponding
single pumps are available.
When put into service, a master and slave
are defined, see also chapter4.3.
A single pump that does not exist as
a double pump type cannot be confi-
gured as a double pump.
ATTENTION!
Содержание Wilo-Stratos -Z
Страница 2: ...Fig 1a Fig 1b Fig 2a Fig 3 Fig 2b...
Страница 3: ...Fig 5 Fig 4 Fig 6 Fig 7...
Страница 4: ...Fig 8 Fig 9 Fig 11 Fig 10 Fig 12...
Страница 6: ...Fig 15 Fig 15 LON Fig 15 PLR Fig 15 SBM Fig 15 Ext Min Fig 15 Ext Off...
Страница 14: ...DEUTSCH 8 Displaylage horizontal vertikal Lageeinstellung in Men punkt 3...
Страница 41: ...ENGLISH 35 Display position horizontal vertical Position setting in menu point 3...
Страница 95: ...NEDERLANDS 89 Display richting horizontaal vertikaal Instelling van de richting in menu punt 3...
Страница 118: ......