43
makers), destroying magnetic cards,
etc..
If the accessibility of the screws on the motor flange is
not guaranteed, the control module can be separated
from the motor by loosening 2 screws, see chapter
5.1.1.
5.1.3 Insulating the pump in refrigerating/air-
conditioning systems
The Wilo Stratos series is suitable for use in refrigera-
ting and air-conditioning systems with flow medium
temperatures up to -10 °C. In these cases, the pumps
may also operate intermittently.
The insulation blankets contained in the products de-
livered (fig. 5, pos. 1) are, however, only permitted in
heating systems with flow medium tepmperatures
from +20°C, since these insulation blankets are not
diffusion-proof when enclosing the pump housing.
When using the pumps in refrigerating and air-condi-
tioning systems, diffusion-proof insulation is to be
provided by the customer.
The pump housing may only be insu-
lated up to the interstice with the
motor, so that the condensation
vents remain free and any condensa-
tion produced in the motor can run
off without hindrance (fig. 6).
To protect it from corrosion, the pump housing is cata-
phoretically coated.
5.2
Electrical connection
Electrical connection should be made by a
qualified electrician. Current national re-
gulations must be observed (e.g. VDE re-
gulations in Germany).
x
According to Part 1 of the VDE 0730, the pump must
be connected to the electrical supply by a solid wire
(3 x 1,5mm
2
minimum cross-section) equipped with a
plug or an all-pole switch. The width of the contact
gap must be at least 3 mm.
x
No motor protection is required. If this is already pre-
sent in the installation, it is be bypassed or set to the
maximum possible current value.
x
To guarantee protection against dripping water and
the grip of the cable gland, cables with an adequate
outer diameter are to be used and screwed suffi-
ciently tightly. In addition, the cables in the vicinity of
the cable gland are to be bent into a run-off loop to
drain off any dripping water. Unoccupied cable
glands are to be closed with the available sealing pla-
stic washers and made sufficiently tight.
x
To adapt the connecting leads to the inner diameter
of the cable entries, the seals consist of concentric
rubber rings, the inner one(s) of which can be remo-
ved if required.
ATTENTION!
Cables of an appropriate outer dia-
meter are to be used, so that the ca-
ble gland is sealed after being tighte-
ned. Unused cable glands are sealed
with a plastic washer. This washer
must not be removed. Even unused
cable glands are to be tightened.
x
When using the pump in systems where the water
temperature exceeds 90 °C, a connecting pipe with
corresponding heat resistance must be used.
x
The connecting lead must be laid in such a way that
it never touches the pipework and/or the pump and
motor casing.
x
This pump may be protected with an FI safety switch.
Identification symbol: FI -
or
x
Check that the mains current and voltage comply
with the data on the rating plate.
x
Mains fuse: see rating plate
x
Pump/installation must be earthed in compliance
with regulations.
In insulation tests with a high-vol-
tage generator the pump is to be di-
sconnected on all poles from the
mains in the control module. The free
cable ends are to be insulated in ac-
cordance with the voltage of the
high-voltage generator.
5.2.1 Electrical pump connection (Figure 7)
x
L, N,
: Mains voltage: single-phase current 1 ~
230 V
AC
, 50 Hz, DIN IEC 38.
x
SSM:
A built-in collective fault signal is available on
the SSM terminals as a potential-free closed contact.
Permissible contact load:
x
minimum: 12 V DC,
10 mA,
x
maximum: 250 V AC, 1 A.
x
Double pumps:
Both motors in the double pump are
to be provided with a separate mains cable and a se-
parate mains fuse protection.
If a single motor in a double pump is
switched off-load, the built-in dou-
ble-pump management is deactiva-
ted.
x
Switching frequency:
x
On-/Off switching by mains supply
≤
20/24 h
x
On-/Off switching by Ext. Off or 0…10 V Signal
≤
20 h
x
Assignment of supply terminals:
The following table
shows the possibilities for which combinations of cir-
cuits the individual cable glands in a cable can be as-
signed. DIN EN 60204-1 (VDE 0113, p.1) is to be ob-
served:
ATTENTION!
ATTENTION!
ATTENTION!
Содержание Wilo-Stratos -Z
Страница 2: ...Fig 1a Fig 1b Fig 2a Fig 3 Fig 2b...
Страница 3: ...Fig 5 Fig 4 Fig 6 Fig 7...
Страница 4: ...Fig 8 Fig 9 Fig 11 Fig 10 Fig 12...
Страница 6: ...Fig 15 Fig 15 LON Fig 15 PLR Fig 15 SBM Fig 15 Ext Min Fig 15 Ext Off...
Страница 14: ...DEUTSCH 8 Displaylage horizontal vertikal Lageeinstellung in Men punkt 3...
Страница 41: ...ENGLISH 35 Display position horizontal vertical Position setting in menu point 3...
Страница 95: ...NEDERLANDS 89 Display richting horizontaal vertikaal Instelling van de richting in menu punt 3...
Страница 118: ......