ENGLISH
53
Modultype
Function
1)
Serial digital
interface PLR
for connecting to the
building management system BMS via Wilo
1xMA
interface converter or customer's coupling module
1xSL
Serial digital
interface LON
for connecting to
LONWORKS networks, transceiver FTT 10A
1xSL
1xMA
Input for potential-free closed contact with the
function "Ext. Off"
2)
Control input "0...10 V"
1xSL
1xMA
for remote speed or set point adjustment
3)
Input for potential-free closed contact with the
function "Ext. Min"
4)
Control input "0...10 V"
1xSL
1xMA
for remote speed or set point adjustment
3)
Operating message SBM
as potential-free opened contact
5)
Control input "0...10 V"
1xMA
for remote speed or set point adjustment
3)
1xSL
IF modul Stratos PLR
IF modul Stratos LON
IF modul Stratos Ext. Off
IF modul Stratos Ext. Min
IF modul Stratos SBM
MA=Master
SL=Slave
9.2.1 Functions of the digital interfaces and
control inputs/output s in double-pump mode
1) The functions of the digital interfaces and/or con-
trol inputs affect the double pump as an entire set,
see chapter 9.1. Connections are made to the MA
only.
2) Bother drives idle.
3) The control input 0...10V has various additional
functions (fig. 12), see table below.
4) The basic load pump runs at min. speed, the other
drive idles.
5) The SBM contact closes if the corresponding drive
is running (single operating readings separately for
MA and SL).
Содержание Wilo-Stratos -Z
Страница 2: ...Fig 1a Fig 1b Fig 2a Fig 3 Fig 2b...
Страница 3: ...Fig 5 Fig 4 Fig 6 Fig 7...
Страница 4: ...Fig 8 Fig 9 Fig 11 Fig 10 Fig 12...
Страница 6: ...Fig 15 Fig 15 LON Fig 15 PLR Fig 15 SBM Fig 15 Ext Min Fig 15 Ext Off...
Страница 14: ...DEUTSCH 8 Displaylage horizontal vertikal Lageeinstellung in Men punkt 3...
Страница 41: ...ENGLISH 35 Display position horizontal vertical Position setting in menu point 3...
Страница 95: ...NEDERLANDS 89 Display richting horizontaal vertikaal Instelling van de richting in menu punt 3...
Страница 118: ......