background image

©

2019 WEINZIERL ENGINEERING GmbH 

Page 14/16

 

Reaction on ‘OFF’ telegram 

This parameter can be used to set whether an OFF telegram on 
the object of the staircase function should be processed or ig-
nored. 

Time for warning before switch off 

The time between pre-warning and deactivation is configured, or 
the pre-warning is deactivated with this parameter. If the pre-
warning time is longer than the actual follow-up time, no pre-
warning is carried out. 

Time of interrupt 

The pre-warning is indicated by a brief interruption (switch off -> 
switch on). The duration of this interrupt is configured in this 
parameter. 

LED lamps often have a long follow-up time, in which 
the lamp still lights even though it is already switched 
off. With such lamps longer interrupt times must be set 
to generate a "visible" interruption. 

Function (Valve actuator) 

The function valve actuator is foreseen to control thermoelectric 
valve drives which are used for floor heating but also for radia-
tors. It maps the continuous position (0% - 100%) to an ongoing 
On/Off sequence called PWM (pulse width modulation) signal. 

If the valve actuator is selected on the parameter page "Actuator 
B: General", a group object for the valve actuator appears in-
stead of the normal switching object. This allows the current 
PWM at the output to be set via KNX (0% - 100%). An additional 
parameter page "Actuator B: Valve actuator" appears for the 
configuration of the valve actuator. 

The received control value is saved automatically by the device, 
to continue faultless after a possible bus power loss. 

Group object 

Type KNX 

Size 

Direction 

GO 74 Actuator B: Valve actuator (PWM) 
- Control value 

5.001 

1 Byte 

From KNX 

 

P. 

Actuator B: Valve actuator 

 

 

Cyclic time (PWM) 

The cyclic time of the PWM, which is used to control a servo 
drive, is configured with this parameter. One cycle involves a 
time range in which the output is switched on and one in which 
the output is switched off. The cyclic time corresponds to the 
period between two rising edges (state change at the output 
from OFF to ON). The longer the flow of the heating circuit (tube 
/ pipe length), the higher the cyclic time should be set. 

Typical thermal servos require several minutes for a 
100% valve change. 

Maximum control value (PWM) 

This parameter can be used to limit the maximum control value. 
The control value is expressed in percent and de-fines the period 
during which the output is switched on in one cycle. 

Example

Cyclic time = 10 Min. 
Maximum control value (PWM) = 80 % 
Maximal output state = ON - 8 min / OFF - 2 min 

Stuck protection 

With the stuck protection, it is intended to prevent the valve from 
being damaged by corrosion or calcification, that it can no longer 
be moved. In case stuck protection is enabled, this is only trig-
gered if the value is permanently 0 % or 100 %. On every other 
control value the servo already moves, so there is no need for a 
stuck protection. 

Control value 0%  

 Open servo for the set time 

Control value 100% 

 Close servo for the set time 

In case the valve is not allowed to open, the stuck protection 
must be disabled. 

Execution time 

If the stuck protection is activated, this parameter is used to set 
the duration of the state change. 

Monitoring interval 

If the stuck protection is activated, this parameter sets the moni-
toring interval. If the state of the output remains un-changed for 
this time, the lock protection is triggered. 

Protection on missing control value 

This parameter enables the protection function on missing con-
trol value telegrams. This is necessary in order to prevent un-
wanted and uncontrolled overheating or cooling down of the 
room, when the control value is missing. 

Protection takes effect, as soon as no telegrams are received 
from the controller over a longer period of time. As soon as this 
extended telegram pause has occurred, it can be assumed that 
the corresponding controller has failed or the connection be-
tween the controller and the valve actuator has been interrupted. 

Protection control value (PWM) 

If the protection on missing control value is enabled, this pa-
rameter sets a protection control value. This configured PWM 
value will set the output, if the protection is active. 

As soon as telegrams from the controller are received again, the 
protection control value (PWM) is overwritten by the received 
value. The protection does not react again, until the waiting time 
in the set monitoring interval is exceeded between individual 
telegrams. 

Monitoring interval 

If the protection on missing control value is enabled, this pa-
rameter sets the monitoring interval. If no further telegram is 
received by the device during this time, the protection function 
takes effect. 

Lock function (with valve actuator) 

With this parameter the lock function can be disabled or enabled. 
If this functionality is activated, the associated group objects as 
well as the parameter page “Actuator 1: Lock function” are dis-
played for further configuration. If the lock has been activated via 
the group object "Lock", the received switching telegrams are not 
executed. 

In addition to the lock object, there is also a priority object, which 
can be used to set a control value independently of the lock. 
Thus, it is possible to set an output PWM without affecting other 
functions. 

Содержание 1D1O

Страница 1: ... Pressing button A long switches to manual operation of the dimming actuator channel channel A This is indicated by cyclic one time flashing of the LED Ch M in orange Pressing button B long switches to manual operation of the switching actuator channel channel B This is indicated by cyclic two time flashing of the LED Ch M in orange In manual operation the respective channel can be switched on by ...

Страница 2: ...stance of the output Between 0 and 100 the switching losses caused by the PWM are added Overall there is a maximum power loss in the upper dimming range The rated power of 144W refers to the maximum permitted ambient temperature for free installation If there are other devic es next to the dimming actuator that emit heat the power that can be connected is reduced Alternatively the devices can also...

Страница 3: ...e dimmer output switches off and an ON telegram is sent via the respective object The output is disabled for the duration of the error state if it is resolved the respective object sends an OFF telegram and the dimmer can be used normally again Overload is triggered from a load of 8A overtemperature from a measured temperature of 85 C in the load section If no value is received by the load section...

Страница 4: ...value scene slumber function or sequencer During manual override values of object 20 are ignored each manual override restarts the fallback time After the fallback time set in the parameter has elapsed the values received on object 20 are processed again Via object 19 the automatic can be switched on or off at any time it also serves as a state object for automatic mode Slumber function The slumbe...

Страница 5: ...ays visible values are used Dimming value on ON telegram night If the dimmer is in night mode this value is activated by ON telegram via object 11 and suitable parameterization Dimming value on OFF telegram night If the dimmer is in night mode this value is activated by OFF telegram via object 11 and suitable parameterization Fade time for day night switching This fade time is only active if switc...

Страница 6: ... of the dimmer Use brightness max value of red green blue The largest value of the 3 bytes is used to control the brightness of the dimmer Minimal value for changing color by object This parameter can be used to configure which minimum dim ming value can be set via object 14 If a value below the mini mum value is received the dimmer is controlled with the minimal value Maximal value for changing c...

Страница 7: ...dims to orientation light The period refers to a complete dimming pro cess of 0 100 Reaction on OFF telegram Here it can be set how the staircase function behaves in the event of an OFF telegram The following options are available Ignore No reaction of the channel on OFF telegram Switch off Switch to switch off value from the parameters Switch to switch off delay The delay time is started with OFF...

Страница 8: ...KNX Size Direction GO 18 Dimmer A Scene Activ Lrn 18 001 1 Byte From KNX Fade time on activation of scene Here the period can be set in which the received scene is dimmed to The period refers to a complete dimming process of 0 100 Scene 1 16 These parameters can be used to configure the reaction of the channel when the respective scene is received It is available No reaction Dimming value The outp...

Страница 9: ...rior dimming abs Set value 5 001 1 Byte From KNX If the lock was activated by object 22 other received telegrams for dimmer automatic mode slumber scene function and se quencer are not executed In addition to the lock object 3 priority objects become visible when the lock function is activated with which the dimmer can be controlled independently of the lock This makes it possible to set an initia...

Страница 10: ... On next activated step The sequence is continued with the next activated step the next step can be activated by object or time controlled Off time Only visible if the sequence is to be continued after off time with this parameter the off time can be configured Step after man operation This step is executed when resuming after manual operation the function of the set step is always executed regard...

Страница 11: ...t the same time Start by scene number When using this start condition the following object becomes visible Group object Type KNX Size Direction GO 31 Dimmer A Sequence scene Activate step 18 001 1 Byte From KNX A telegram with the set scene on this object activates the respec tive step the sequence is then continued according to its config uration from this step onwards All steps with this start c...

Страница 12: ...unctions Group object Type KNX Size Direction GO 75 Actuator B Lock Activate 1 001 1 Bit From KNX GO 76 Actuator B Prior output Switch 1 001 1 Bit From KNX Example of the priority object In the case of events in public buildings or in restaurants the normal operation can be set into an inoperative state by the lock group object Thus it is possible to lock during the lecture or concert switches tha...

Страница 13: ...lected on the parameter page Actuator B General delayed switching times can be con figured The Actuator B On Off Delay parameter page is displayed for this purpose Group object Type KNX Size Direction GO 71 Actuator B Output Switch 1 001 1 Bit From KNX N Actuator B On Off delay On delay time The duration of the switch on delay is configured in this parame ter Input 1 0 Output T 1 0 Off delay time ...

Страница 14: ...in Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enabled this is only trig gered if the value is permanently 0 or 100 On every other control value the servo already moves so there is no need for a stuck protection Control value 0 Open servo for the set time C...

Страница 15: ...nction type Timer The timer specific parameters and group objects are available Function type Logic The logic specific parameters and group objects are available These additional logic and timer functions can be linked to one another by means of the associated group objects This also allows to create complex structures For this purpose the output of a function is set to the same group address as t...

Страница 16: ... output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are switched off 0 Gate type XNOR gate The output is triggered on 1 if both inputs are equal Gate type INVERTER Input on 1 is converted into output off 0 Input off 0 is con verted into outp...

Отзывы: