2019 WEINZIERL ENGINEERING GmbH 

Page 3/16

 

Send delay after bus power return 

A send delay of telegrams after the return of the bus voltage can 
be set via this parameter. In this case, telegrams from the device 
are sent to the KNX bus in a delayed manner by the set time. 
This results in a reduction of the bus load at a bus power return. 
Other functions such as receiving telegrams of switching opera-
tions of the actuator are not affected by this parameter. 

Prog. mode on device front 

In addition to the normal programming button 

 the device 

allows activating the programming mode on the device front 
without opening the switchboard cover. The programming mode 
can be activated and deactivated via pressing simultaneously 
both buttons 

 and 

.  

This feature can be enabled and disabled via the parameter 
“Prog. mode on device front”. The recessed programming button 

 (next to the Programming LED 

) is always enabled and 

not influenced by this parameter.  

Manual operation on device 

This parameter is used to configure the manual operation on the 
device. The manual operation mode can be disabled or activated 
(with or without time limitation). The time limit defines the dura-
tion until the automatic return from the manual operation mode 
back into the normal operating mode. 

The device is in normal operating mode when the manual control 
is not active. In the manual operating mode, received switching 
telegrams are ignored. When the manual operation mode is 
terminated (after expiry of the time limit or manually), the last 
state of the outputs remains, until a new switching telegram is 
received again. 

The following options are selectable: 

 

Disabled 

 

Enabled with time limit 1 min 

 

Enabled with time limit 10 min 

 

Enabled with time limit 30 min 

 

Enabled without time limit 

Heartbeat 

Cyclic sending of values to the KNX-Bus, to indicate that the 
device is operational. For the Cycle time values between 1 min 
and 24h are selectable. 

 
Alarm objects for error conditions 

With this parameter, the following objects for the visualization of 
error states become visible: 

 
If an error condition is detected, the dimmer output switches off 
and an ON telegram is sent via the respective object. The output 
is disabled for the duration of the error state, if it is resolved, the 
respective object sends an OFF telegram, and the dimmer can 
be used normally again. 

Overload is triggered from a load of 8A, overtemperature from a 
measured temperature of 85°C in the load section. If no value is 

received by the load section for longer than 3 seconds, the error 
state "No supply voltage" is triggered. 

PWM frequency 

Here can be switched between 480Hz and 600Hz PWM fre-
quency. 

C. 

Dimmer A: General 

 

 

Name (30 Characters) 

An arbitrary name can be assigned for the channel. However, 
this should be clear and meaningful, this makes it easier to work 
with the associated group objects, because the given name is 
displayed there as a label. If no name is assigned, the group 
objects 

are named „Dimmer A“. 

Function 

This parameter defines the functionality of the actuator, the 
following options are selectable: 

 

Disabled 

 

Dimmer 
When this functionality is selected, scene function, au-
tomatic mode, slumber and lock function are available. 
In the "Dimmer" function, objects for switching on/off, 
relative dimming, dimmer control via dimming and 
RGB value can be configured. The parameter page 
"Dimmer A: Dimmer" is displayed. 

 

Staircase function 
The parameter page "Dimmer A: Staircase function" is 
displayed. Only the lock function is available here. 

When a function is selected, the following parameters appear: 

Send state 

This parameter defines the behavior of the state objects: 

 

Disabled 
State objects are deactivated and not displayed. 

 

Only on read 
State objects send only on request. 

 

On change 
The switch object sends an OFF telegram when the 
output value changes to 0%, an ON telegram when the 
output value changes from 0% to a value greater than 
0%. The value object transmits with a time interval of 
at least 1 second if the value at the output has 
changed by at least 1% or if a dimming process has 
been completed. 

 

Cyclic and on change 
State objects send cyclically and on value change. 
 

Group object 

Type KNX 

Size 

Direction 

GO 1 Heartbeat - Trigger 

1.001 

1 Bit 

To KNX 

Group object 

Type KNX 

Size 

Direction 

GO 2 Alarm - Overload 

1.001 

1 Bit 

To KNX 

GO 3 Alarm - Overtemperature 

1.001 

1 Bit 

To KNX 

GO 4 Alarm - No supply voltage 

1.001 

1 Bit 

To KNX 

Содержание 1D1O

Страница 1: ... Pressing button A long switches to manual operation of the dimming actuator channel channel A This is indicated by cyclic one time flashing of the LED Ch M in orange Pressing button B long switches to manual operation of the switching actuator channel channel B This is indicated by cyclic two time flashing of the LED Ch M in orange In manual operation the respective channel can be switched on by ...

Страница 2: ...stance of the output Between 0 and 100 the switching losses caused by the PWM are added Overall there is a maximum power loss in the upper dimming range The rated power of 144W refers to the maximum permitted ambient temperature for free installation If there are other devic es next to the dimming actuator that emit heat the power that can be connected is reduced Alternatively the devices can also...

Страница 3: ...e dimmer output switches off and an ON telegram is sent via the respective object The output is disabled for the duration of the error state if it is resolved the respective object sends an OFF telegram and the dimmer can be used normally again Overload is triggered from a load of 8A overtemperature from a measured temperature of 85 C in the load section If no value is received by the load section...

Страница 4: ...value scene slumber function or sequencer During manual override values of object 20 are ignored each manual override restarts the fallback time After the fallback time set in the parameter has elapsed the values received on object 20 are processed again Via object 19 the automatic can be switched on or off at any time it also serves as a state object for automatic mode Slumber function The slumbe...

Страница 5: ...ays visible values are used Dimming value on ON telegram night If the dimmer is in night mode this value is activated by ON telegram via object 11 and suitable parameterization Dimming value on OFF telegram night If the dimmer is in night mode this value is activated by OFF telegram via object 11 and suitable parameterization Fade time for day night switching This fade time is only active if switc...

Страница 6: ... of the dimmer Use brightness max value of red green blue The largest value of the 3 bytes is used to control the brightness of the dimmer Minimal value for changing color by object This parameter can be used to configure which minimum dim ming value can be set via object 14 If a value below the mini mum value is received the dimmer is controlled with the minimal value Maximal value for changing c...

Страница 7: ...dims to orientation light The period refers to a complete dimming pro cess of 0 100 Reaction on OFF telegram Here it can be set how the staircase function behaves in the event of an OFF telegram The following options are available Ignore No reaction of the channel on OFF telegram Switch off Switch to switch off value from the parameters Switch to switch off delay The delay time is started with OFF...

Страница 8: ...KNX Size Direction GO 18 Dimmer A Scene Activ Lrn 18 001 1 Byte From KNX Fade time on activation of scene Here the period can be set in which the received scene is dimmed to The period refers to a complete dimming process of 0 100 Scene 1 16 These parameters can be used to configure the reaction of the channel when the respective scene is received It is available No reaction Dimming value The outp...

Страница 9: ...rior dimming abs Set value 5 001 1 Byte From KNX If the lock was activated by object 22 other received telegrams for dimmer automatic mode slumber scene function and se quencer are not executed In addition to the lock object 3 priority objects become visible when the lock function is activated with which the dimmer can be controlled independently of the lock This makes it possible to set an initia...

Страница 10: ... On next activated step The sequence is continued with the next activated step the next step can be activated by object or time controlled Off time Only visible if the sequence is to be continued after off time with this parameter the off time can be configured Step after man operation This step is executed when resuming after manual operation the function of the set step is always executed regard...

Страница 11: ...t the same time Start by scene number When using this start condition the following object becomes visible Group object Type KNX Size Direction GO 31 Dimmer A Sequence scene Activate step 18 001 1 Byte From KNX A telegram with the set scene on this object activates the respec tive step the sequence is then continued according to its config uration from this step onwards All steps with this start c...

Страница 12: ...unctions Group object Type KNX Size Direction GO 75 Actuator B Lock Activate 1 001 1 Bit From KNX GO 76 Actuator B Prior output Switch 1 001 1 Bit From KNX Example of the priority object In the case of events in public buildings or in restaurants the normal operation can be set into an inoperative state by the lock group object Thus it is possible to lock during the lecture or concert switches tha...

Страница 13: ...lected on the parameter page Actuator B General delayed switching times can be con figured The Actuator B On Off Delay parameter page is displayed for this purpose Group object Type KNX Size Direction GO 71 Actuator B Output Switch 1 001 1 Bit From KNX N Actuator B On Off delay On delay time The duration of the switch on delay is configured in this parame ter Input 1 0 Output T 1 0 Off delay time ...

Страница 14: ...in Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enabled this is only trig gered if the value is permanently 0 or 100 On every other control value the servo already moves so there is no need for a stuck protection Control value 0 Open servo for the set time C...

Страница 15: ...nction type Timer The timer specific parameters and group objects are available Function type Logic The logic specific parameters and group objects are available These additional logic and timer functions can be linked to one another by means of the associated group objects This also allows to create complex structures For this purpose the output of a function is set to the same group address as t...

Страница 16: ... output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are switched off 0 Gate type XNOR gate The output is triggered on 1 if both inputs are equal Gate type INVERTER Input on 1 is converted into output off 0 Input off 0 is con verted into outp...

Отзывы: