2019 WEINZIERL ENGINEERING GmbH
Page 13/16
Function (Universal output)
If the universal output is selected on the parameter page "Actua-
tor B: General", the actuator can be used as a switching output.
A parameter for the scene function is also dis-played.
Group object
Type KNX
Size
Direction
GO 71 Actuator A: Output - Switch
1.001
1 Bit
From KNX
Scene function
With this parameter the scene function can be enabled or disa-
bled. If this functionality is enabled, the respective group object
as well as the parameter page "Actuator B: Scene function" are
displayed for further configuration of scenes 1-16.
Group object
Type KNX
Size
Direction
GO 72 Actuator A: Scene - Activ./Lrn.
18.001
1 Bit
From KNX
M. Actuator B: Scene function
Scene 1-16
These parameters can be used to configure the state, which is
set at the output when the respective scene is executed.
The following options are selectable:
No reaction
Switch on
Switch off
Learnable
By using a scene control telegram, the current state at
the output can be saved for the respective scene. This
allows the user to customize the scene without ETS
download.
Number
This parameter sets any scene number between 1 and 64 to the
scene. There must not configured any scene numbers twice.
Function (On/Off delay)
If the ON/OFF delay is selected on the parameter page "Actuator
B: General", delayed switching times can be con-figured. The
"Actuator B: On/Off Delay" parameter page is displayed for this
purpose.
Group object
Type KNX
Size
Direction
GO 71 Actuator B: Output - Switch
1.001
1 Bit
From KNX
N.
Actuator B: On/Off delay
On delay time
The duration of the switch-on delay is configured in this parame-
ter.
Input
-------1------------------0----------
Output
-------|-T-1--------------0----------
Off delay time
The duration of the switch-off delay is configured in this parame-
ter.
Input
-------1------------------0----------
Output
-------1------------------|-T-0------
Retriggerable
If these parameters are activated, the respective delay time is
restarted upon receipt of the corresponding switching signal.
Function (Staircase function)
If the staircase function is selected on the parameter page "Ac-
tuator B: General", a group object for the staircase function
appears in addition to the normal switching object. Via the addi-
tional parameter page "Actuator B: Staircase function" this func-
tion can be configured.
Group object
Type KNX
Size
Direction
GO 71 Actuator B: Output - Switch
1.001
1 Bit
From
KNX
GO 73 Actuator B: Staircase function -
Trigger
1.010
1 Bit
From
KNX
O. Actuator B: Staircase function
Switch off time
The time for which the output is activated after an ON tele-gram
(object of the staircase function) has been received, can set in
this parameter.
Input
-------1------------------0----------
Output
-------1-T-0-------------------------
Retriggerable
This parameter can be used to set whether the follow-up time is
to be restarted when an ON telegram is received on the object of