2019 WEINZIERL ENGINEERING GmbH 

Page 5/16

 

Behavior on OFF telegram 

This parameter describes the behavior of the dimmer when an 
OFF telegram is sent via object 11. 

It is available: 

 

No reaction 

 

Dim to fix value 

Dimming value on OFF telegram 

This value is activated by OFF telegram via object 11 with suita-
ble parameterization. 

Behavior on 2. OFF telegram 

This parameter describes the behavior of the dimmer when a 2. 
OFF telegram is received via object 11. 

It is available: 

 

No reaction 

 

Switch off 

The 2. OFF telegram must follow the 1. OFF telegram within 1 
second in order to be evaluated. If the current brightness is 
equal to or lower than the parameterized brightness for OFF 
telegram, the device is already switched off by the 1. OFF tele-
gram. 

Fade time on OFF telegram 

This fade time is active when an OFF telegram is received. The 
period refers to a complete dimming process of 0-100%. 

Day/night switching 

When using this function, the following objects are visible for 
switching between day/night mode: 

Group object 

Type KNX 

Size 

Direction 

GO 15 Dimmer A: Day/Night - Switch 

1.001 

1 Bit 

From KNX 

 
Day mode is triggered with an ON telegram on object 15, night 
mode with an OFF telegram. After a restart, the device is in day 
mode. 

In addition, it can be determined when the values become active 
after receiving a telegram on these objects, it is available: 

 

Disabled 

 

Switch on day/night telegram 
Immediately after reception of day/night switching, it is 
dimmed to the active value according to the last 
switch-on/switch-off received via object 11. 

 

Switch on next on/off telegram 
The currently active value is not used until the next 
switch on/off telegram via object 11. 

There is a separate switch-on and switch-off value for night 
mode in the parameters, in day mode the always visible values 
are used. 

Dimming value on ON telegram (night) 

If the dimmer is in night mode, this value is activated by ON 
telegram via object 11 and suitable parameterization. 

Dimming value on OFF telegram (night) 

If the dimmer is in night mode, this value is activated by OFF 
telegram via object 11 and suitable parameterization. 

 

Fade time for day/night switching 

This fade time is only active if switching on day/night telegram is 
used. If switching on next on/off telegram is used, the regular 
fade time of the respective on or off telegram is active. The 
period refers to a complete dimming process of 0-100%. 

Object Dimming rel. 

 

The following object is available for dimming using relative dim-
ming commands, if activated via parameters: 

Group object 

Type KNX 

Size 

Direction 

GO 12 Dimmer A: Dimming rel. - 
Brighter/Darker 

3.007 

4 Bit 

From KNX 

 

Minimal dimming value while dimming with object 

This parameter can be used to set which minimum dimming 
value can be achieved via relative dimming. If the current dim-
ming value is below the minimum value, the brightness cannot 
be reduced via object 12. 

Maximal dimming value while dimming with object 

This parameter can be used to set which maximum dimming 
value can be achieved via relative dimming. If the current dim-
ming value is above the maximum value, the brightness cannot 
be increased via object 12. 

Fade time while dimming brighter with object 

This fade time is active when the brightness is increased by 
relative dimming with object 12. The period refers to a complete 
dimming process of 0-100%. 

Fade time while dimming darker with object 

This fade time is active when the brightness is decreased by 
relative dimming with object 12. The period refers to a complete 
dimming process of 0-100%. 

Object Dimming value 

 

The following object is used to control the dimmer via dimming 
value if it has been activated via parameters: 

Group object 

Type KNX 

Size 

Direction 

GO 13 Dimmer A: Dimming abs. - Set 
value 

5.001 

1 Byte 

From KNX 

Содержание 1D1O

Страница 1: ... Pressing button A long switches to manual operation of the dimming actuator channel channel A This is indicated by cyclic one time flashing of the LED Ch M in orange Pressing button B long switches to manual operation of the switching actuator channel channel B This is indicated by cyclic two time flashing of the LED Ch M in orange In manual operation the respective channel can be switched on by ...

Страница 2: ...stance of the output Between 0 and 100 the switching losses caused by the PWM are added Overall there is a maximum power loss in the upper dimming range The rated power of 144W refers to the maximum permitted ambient temperature for free installation If there are other devic es next to the dimming actuator that emit heat the power that can be connected is reduced Alternatively the devices can also...

Страница 3: ...e dimmer output switches off and an ON telegram is sent via the respective object The output is disabled for the duration of the error state if it is resolved the respective object sends an OFF telegram and the dimmer can be used normally again Overload is triggered from a load of 8A overtemperature from a measured temperature of 85 C in the load section If no value is received by the load section...

Страница 4: ...value scene slumber function or sequencer During manual override values of object 20 are ignored each manual override restarts the fallback time After the fallback time set in the parameter has elapsed the values received on object 20 are processed again Via object 19 the automatic can be switched on or off at any time it also serves as a state object for automatic mode Slumber function The slumbe...

Страница 5: ...ays visible values are used Dimming value on ON telegram night If the dimmer is in night mode this value is activated by ON telegram via object 11 and suitable parameterization Dimming value on OFF telegram night If the dimmer is in night mode this value is activated by OFF telegram via object 11 and suitable parameterization Fade time for day night switching This fade time is only active if switc...

Страница 6: ... of the dimmer Use brightness max value of red green blue The largest value of the 3 bytes is used to control the brightness of the dimmer Minimal value for changing color by object This parameter can be used to configure which minimum dim ming value can be set via object 14 If a value below the mini mum value is received the dimmer is controlled with the minimal value Maximal value for changing c...

Страница 7: ...dims to orientation light The period refers to a complete dimming pro cess of 0 100 Reaction on OFF telegram Here it can be set how the staircase function behaves in the event of an OFF telegram The following options are available Ignore No reaction of the channel on OFF telegram Switch off Switch to switch off value from the parameters Switch to switch off delay The delay time is started with OFF...

Страница 8: ...KNX Size Direction GO 18 Dimmer A Scene Activ Lrn 18 001 1 Byte From KNX Fade time on activation of scene Here the period can be set in which the received scene is dimmed to The period refers to a complete dimming process of 0 100 Scene 1 16 These parameters can be used to configure the reaction of the channel when the respective scene is received It is available No reaction Dimming value The outp...

Страница 9: ...rior dimming abs Set value 5 001 1 Byte From KNX If the lock was activated by object 22 other received telegrams for dimmer automatic mode slumber scene function and se quencer are not executed In addition to the lock object 3 priority objects become visible when the lock function is activated with which the dimmer can be controlled independently of the lock This makes it possible to set an initia...

Страница 10: ... On next activated step The sequence is continued with the next activated step the next step can be activated by object or time controlled Off time Only visible if the sequence is to be continued after off time with this parameter the off time can be configured Step after man operation This step is executed when resuming after manual operation the function of the set step is always executed regard...

Страница 11: ...t the same time Start by scene number When using this start condition the following object becomes visible Group object Type KNX Size Direction GO 31 Dimmer A Sequence scene Activate step 18 001 1 Byte From KNX A telegram with the set scene on this object activates the respec tive step the sequence is then continued according to its config uration from this step onwards All steps with this start c...

Страница 12: ...unctions Group object Type KNX Size Direction GO 75 Actuator B Lock Activate 1 001 1 Bit From KNX GO 76 Actuator B Prior output Switch 1 001 1 Bit From KNX Example of the priority object In the case of events in public buildings or in restaurants the normal operation can be set into an inoperative state by the lock group object Thus it is possible to lock during the lecture or concert switches tha...

Страница 13: ...lected on the parameter page Actuator B General delayed switching times can be con figured The Actuator B On Off Delay parameter page is displayed for this purpose Group object Type KNX Size Direction GO 71 Actuator B Output Switch 1 001 1 Bit From KNX N Actuator B On Off delay On delay time The duration of the switch on delay is configured in this parame ter Input 1 0 Output T 1 0 Off delay time ...

Страница 14: ...in Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enabled this is only trig gered if the value is permanently 0 or 100 On every other control value the servo already moves so there is no need for a stuck protection Control value 0 Open servo for the set time C...

Страница 15: ...nction type Timer The timer specific parameters and group objects are available Function type Logic The logic specific parameters and group objects are available These additional logic and timer functions can be linked to one another by means of the associated group objects This also allows to create complex structures For this purpose the output of a function is set to the same group address as t...

Страница 16: ... output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are switched off 0 Gate type XNOR gate The output is triggered on 1 if both inputs are equal Gate type INVERTER Input on 1 is converted into output off 0 Input off 0 is con verted into outp...

Отзывы: