2019 WEINZIERL ENGINEERING GmbH
Page 16/16
The output value can be inverted by parameter
‘Output’. (Not inverted / inverted)
Input
-------1------------------0----------
Output
-------|-T-1--------------|-T-0------
Group object
Type KNX Size
Direction
Timer - Switch-on/off delayed - Input
1.002
1 Bit
From KNX
Timer - Switch-on/off delayed - Output
1.002
1 Bit
To KNX
Timer type (Impulse (Staircase))
Timer with impulse that - after being switched
ON
-
automatical-
ly switches OFF
after a defined duration defined in
‘Delay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’. (Not inverted / inverted)
Input
-------1------------------0----------
Output
-------1-T-0-------------------------
Group object
Type
KNX
Size
Direction
Timer - Switch-impulse (staircase) - Input
1.002
1 Bit
From KNX
Timer - Switch-impulse (staircase) - Output
1.002
1 Bit
To KNX
Each timer can be stopped by sending the opposite val-
ue to its input group object.
For example:
An already started switch on timer can be stopped by
sending OFF (0) to its input group object.
T.
Function 1 - 16 (Logic)
Function name (10 Characters)
The function name can be chosen freely.
The name is visible in the group object entry in the ETS soft-
ware. This makes it easier to work with the associated group
objects, because the given name is displayed there as a label.
Gate type (AND gate)
The output is triggered on (1), if both inputs are switched on (1).
Gate type (OR gate)
The output is triggered on (1), if one or both inputs are switched
on (1).
Gate type (XOR gate)
The output is triggered on (1), if the two inputs are not equal.
Gate type (NAND gate)
The output is triggered on (1), if one or both inputs are switched
off (0).
Gate type (NOR gate)
The output is triggered on (1), if both inputs are switched off (0).
Gate type (XNOR gate)
The output is triggered on (1), if both inputs are equal.
Gate type (INVERTER)
Input on (1) is converted into output off (0). Input off (0) is con-
verted into output on (1).
Group Object
Type KNX
Size
Direction
Logic - Gate input - Input
1.002
1 Bit
From KNX
Logic - Gate output - Output
1.002
1 Bit
To KNX
Group object
Type KNX Size
Direction
Logic - Gate input A - Input
1.002
1 Bit
From KNX
Logic - Gate input B - Input
1.002
1 Bit
From KNX
Logic - Gate output - Output
1.002
1 Bit
To KNX
WARNING
The device must be mounted and commis-
sioned by an authorized electrician.
The prevailing safety rules must be heeded.
The device must not be opened.
For planning and construction of electric in-
stallations, the relevant guidelines, regulations
and standards of the respective country are to
be considered.
The device is a permanently connected
equipment: A readily accessible disconnect
device shall be incorporated external to the
equipment.
The installation requires a 16 A fuse for exter-
nal overcurrent protection.
The power rating is indicated on the side of
the product.
ETS4/5 Database
www.weinzierl.de/en/products/532/ets4
Datasheet
www.weinzierl.de/en/products/532/datasheet
CE Declaration
www.weinzierl.de/en/products/532/ce-declaration
Weinzierl Engineering GmbH
D-84508 Burgkirchen / Alz
Germany
www.weinzierl.de
2019/03/05