Weinzierl 1D1O Скачать руководство пользователя страница 16

©

2019 WEINZIERL ENGINEERING GmbH 

Page 16/16

 

The output value can be inverted by parameter  
‘Output’. (Not inverted / inverted) 

Input

 

-------1------------------0----------

 

Output

 

-------|-T-1--------------|-T-0------

 

Group object 

Type KNX  Size 

Direction 

Timer - Switch-on/off delayed - Input 

1.002 

1 Bit 

From KNX 

Timer - Switch-on/off delayed - Output 

1.002 

1 Bit 

To KNX 

 

Timer type (Impulse (Staircase)) 

Timer with impulse that - after being switched 

ON

 - 

automatical-

ly switches OFF

 after a defined duration defined in 

‘Delay time [s]’ parameter. 
The output value can be inverted by parameter  
‘Output’. (Not inverted / inverted) 

Input

 

-------1------------------0----------

 

Output

 

-------1-T-0-------------------------

 

Group object 

Type 
KNX 

Size 

Direction 

Timer - Switch-impulse (staircase) - Input 

1.002 

1 Bit 

From KNX 

Timer - Switch-impulse (staircase) - Output 

1.002 

1 Bit 

To KNX 

 

 Each timer can be stopped by sending the opposite val-
ue to its input group object.  
For example:  
An already started switch on timer can be stopped by 
sending OFF (0) to its input group object. 

 

T. 

Function 1 - 16 (Logic) 

 

Function name (10 Characters) 

The function name can be chosen freely.  
The name is visible in the group object entry in the ETS soft-
ware. This makes it easier to work with the associated group 

objects, because the given name is displayed there as a label. 

 

Gate type (AND gate) 

The output is triggered on (1), if both inputs are switched on (1). 

Gate type (OR gate) 

The output is triggered on (1), if one or both inputs are switched 
on (1). 

Gate type (XOR gate) 

The output is triggered on (1), if the two inputs are not equal. 

Gate type (NAND gate) 

The output is triggered on (1), if one or both inputs are switched 
off (0). 

Gate type (NOR gate) 

The output is triggered on (1), if both inputs are switched off (0). 

Gate type (XNOR gate) 

The output is triggered on (1), if both inputs are equal. 

Gate type (INVERTER) 

Input on (1) is converted into output off (0). Input off (0) is con-
verted into output on (1). 

Group Object 

Type KNX 

Size 

Direction 

Logic - Gate input - Input 

1.002 

1 Bit 

From KNX 

Logic - Gate output - Output 

1.002 

1 Bit 

To KNX 

 

 

 

Group object 

Type KNX  Size 

Direction 

Logic - Gate input A - Input 

1.002 

1 Bit 

From KNX 

Logic - Gate input B - Input 

1.002 

1 Bit 

From KNX 

Logic - Gate output - Output 

1.002 

1 Bit 

To KNX 

    WARNING 

 

 

The device must be mounted and commis-
sioned by an authorized electrician. 

 

The prevailing safety rules must be heeded. 

 

The device must not be opened. 

 

For planning and construction of electric in-
stallations, the relevant guidelines, regulations 
and standards of the respective country are to 
be considered. 

 

The device is a permanently connected 
equipment: A readily accessible disconnect 
device shall be incorporated external to the 
equipment. 

 

The installation requires a 16 A fuse for exter-
nal overcurrent protection. 

 

The power rating is indicated on the side of 
the product. 
 

 

 

 

ETS4/5 Database 

www.weinzierl.de/en/products/532/ets4 

Datasheet 

www.weinzierl.de/en/products/532/datasheet

 

CE Declaration 

www.weinzierl.de/en/products/532/ce-declaration

 

Weinzierl Engineering GmbH

 

D-84508 Burgkirchen / Alz 

Germany 

www.weinzierl.de 

[email protected] 

 

2019/03/05

 

 

Содержание 1D1O

Страница 1: ... Pressing button A long switches to manual operation of the dimming actuator channel channel A This is indicated by cyclic one time flashing of the LED Ch M in orange Pressing button B long switches to manual operation of the switching actuator channel channel B This is indicated by cyclic two time flashing of the LED Ch M in orange In manual operation the respective channel can be switched on by ...

Страница 2: ...stance of the output Between 0 and 100 the switching losses caused by the PWM are added Overall there is a maximum power loss in the upper dimming range The rated power of 144W refers to the maximum permitted ambient temperature for free installation If there are other devic es next to the dimming actuator that emit heat the power that can be connected is reduced Alternatively the devices can also...

Страница 3: ...e dimmer output switches off and an ON telegram is sent via the respective object The output is disabled for the duration of the error state if it is resolved the respective object sends an OFF telegram and the dimmer can be used normally again Overload is triggered from a load of 8A overtemperature from a measured temperature of 85 C in the load section If no value is received by the load section...

Страница 4: ...value scene slumber function or sequencer During manual override values of object 20 are ignored each manual override restarts the fallback time After the fallback time set in the parameter has elapsed the values received on object 20 are processed again Via object 19 the automatic can be switched on or off at any time it also serves as a state object for automatic mode Slumber function The slumbe...

Страница 5: ...ays visible values are used Dimming value on ON telegram night If the dimmer is in night mode this value is activated by ON telegram via object 11 and suitable parameterization Dimming value on OFF telegram night If the dimmer is in night mode this value is activated by OFF telegram via object 11 and suitable parameterization Fade time for day night switching This fade time is only active if switc...

Страница 6: ... of the dimmer Use brightness max value of red green blue The largest value of the 3 bytes is used to control the brightness of the dimmer Minimal value for changing color by object This parameter can be used to configure which minimum dim ming value can be set via object 14 If a value below the mini mum value is received the dimmer is controlled with the minimal value Maximal value for changing c...

Страница 7: ...dims to orientation light The period refers to a complete dimming pro cess of 0 100 Reaction on OFF telegram Here it can be set how the staircase function behaves in the event of an OFF telegram The following options are available Ignore No reaction of the channel on OFF telegram Switch off Switch to switch off value from the parameters Switch to switch off delay The delay time is started with OFF...

Страница 8: ...KNX Size Direction GO 18 Dimmer A Scene Activ Lrn 18 001 1 Byte From KNX Fade time on activation of scene Here the period can be set in which the received scene is dimmed to The period refers to a complete dimming process of 0 100 Scene 1 16 These parameters can be used to configure the reaction of the channel when the respective scene is received It is available No reaction Dimming value The outp...

Страница 9: ...rior dimming abs Set value 5 001 1 Byte From KNX If the lock was activated by object 22 other received telegrams for dimmer automatic mode slumber scene function and se quencer are not executed In addition to the lock object 3 priority objects become visible when the lock function is activated with which the dimmer can be controlled independently of the lock This makes it possible to set an initia...

Страница 10: ... On next activated step The sequence is continued with the next activated step the next step can be activated by object or time controlled Off time Only visible if the sequence is to be continued after off time with this parameter the off time can be configured Step after man operation This step is executed when resuming after manual operation the function of the set step is always executed regard...

Страница 11: ...t the same time Start by scene number When using this start condition the following object becomes visible Group object Type KNX Size Direction GO 31 Dimmer A Sequence scene Activate step 18 001 1 Byte From KNX A telegram with the set scene on this object activates the respec tive step the sequence is then continued according to its config uration from this step onwards All steps with this start c...

Страница 12: ...unctions Group object Type KNX Size Direction GO 75 Actuator B Lock Activate 1 001 1 Bit From KNX GO 76 Actuator B Prior output Switch 1 001 1 Bit From KNX Example of the priority object In the case of events in public buildings or in restaurants the normal operation can be set into an inoperative state by the lock group object Thus it is possible to lock during the lecture or concert switches tha...

Страница 13: ...lected on the parameter page Actuator B General delayed switching times can be con figured The Actuator B On Off Delay parameter page is displayed for this purpose Group object Type KNX Size Direction GO 71 Actuator B Output Switch 1 001 1 Bit From KNX N Actuator B On Off delay On delay time The duration of the switch on delay is configured in this parame ter Input 1 0 Output T 1 0 Off delay time ...

Страница 14: ...in Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enabled this is only trig gered if the value is permanently 0 or 100 On every other control value the servo already moves so there is no need for a stuck protection Control value 0 Open servo for the set time C...

Страница 15: ...nction type Timer The timer specific parameters and group objects are available Function type Logic The logic specific parameters and group objects are available These additional logic and timer functions can be linked to one another by means of the associated group objects This also allows to create complex structures For this purpose the output of a function is set to the same group address as t...

Страница 16: ... output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are switched off 0 Gate type XNOR gate The output is triggered on 1 if both inputs are equal Gate type INVERTER Input on 1 is converted into output off 0 Input off 0 is con verted into outp...

Отзывы: