2019 WEINZIERL ENGINEERING GmbH
Page 11/16
When a step is activated, its parameters for configuration ap-
pear.
In the text box at the top right with the content "Step x", you can
enter your own name for the step. This designation serves for
better orientation of the user and has no influence on the func-
tion of the step.
Start by time
This parameter is used to configure a temporal start condition of
the step.
Disabled
Start condition not used
Start at a fixed time of day
Here the time of day at which the step should start can
be entered. When using this start condition, the current
time must have been received via the following object:
Group object
Type KNX
Size
Direction
GO 5 Time of Day - Set
10.001
3 Byte
From KNX
If no valid time was received by object 5, all
start conditions at fixed times of day are not
active.
The time is continuously updated by the de-
vice through its internal timers, but compo-
nent tolerances always result in a deviation
from the actual time. Therefore, the current
time should be sent to the device by a pre-
cise timer at least twice a day in order to
keep the deviation as small as possible.
-
Start after last trigger
Here you can specify the time interval to wait after the
previous activation before executing the step. This
start condition is not available for step 1.
Start time
Here either the time day or the waiting time can be specified for
the execution of the current step, if a timed start condition is
used.
Start by ON/OFF telegram
When using this start condition, a separate object is available for
each step:
Group object
Type KNX
Size
Direction
GO 35-66 Dimmer A: Sequence Step x
on/off - Switch
1.001
1 Bit
From KNX
An ON telegram to one of these objects activates the respective
step, the sequence is then continued according to its configura-
tion from this step onwards.
An OFF telegram also activates this step, but resets the se-
quence at the same time.
Start by scene number
When using this start condition, the following object becomes
visible:
Group object
Type KNX
Size
Direction
GO 31 Dimmer A: Sequence scene -
Activate step
18.001
1 Byte
From KNX
A telegram with the set scene on this object activates the respec-
tive step, the sequence is then continued according to its config-
uration from this step onwards.
All steps with this start condition are controlled by this object.
Action
When the step is activated, the configured function is executed,
the following functions are available for selection:
None
No function is executed, for example this can be used
to implement a switch-on delay for a sequence.
Start loop
The sequence continues from the selected step. Pa-
rameters for the initial step of the loop and the number
of loops become visible.
Send scene number
When using this function, the following object becomes
visible:
Group object
Type KNX
Size
Direction
GO 32 Dimmer A: Se-
quence Scene - Send
scene
18.001
1 Byte
To KNX
A parameter for the scene number to be sent becomes
visible. When the step is activated, this scene number
is sent via the object.
All steps send the scene number via this object, if this
function is used for the respective step.
Brightness
Parameters for brightness and fade time become visi-
ble. When this step is activated, the dimmer dims from
the current brightness value to the specified brightness
with the parameterized fade time. This time is related
to a complete dimming process of 0-100%.
K.
Actuator B: General
Name (30 Characters)
An arbitrary name can be assigned for the channel. However,
this should be clear and meaningful, this makes it easier to work
with the associated group objects, because the given name is
displayed there as a label. If no name is assigned, the group
objects are named “Actuator B: …”.
Function
This parameter defines the functionality of the actuator.
The following options are selectable:
Disabled
Switch dimmer
Universal output
On/Off delay
Staircase function
Valve actuator (PWM for thermal servo)
If the actuator is not “Disabled”, the following parameters are
displayed: