2019 WEINZIERL ENGINEERING GmbH 

Page 11/16

 

When a step is activated, its parameters for configuration ap-
pear. 

In the text box at the top right with the content "Step x", you can 
enter your own name for the step. This designation serves for 
better orientation of the user and has no influence on the func-
tion of the step. 

Start by time 

This parameter is used to configure a temporal start condition of 
the step. 

 

Disabled 
Start condition not used 

 

Start at a fixed time of day 
Here the time of day at which the step should start can 
be entered. When using this start condition, the current 
time must have been received via the following object: 

Group object 

Type KNX 

Size 

Direction 

GO 5 Time of Day - Set 

10.001 

3 Byte 

From KNX 

If no valid time was received by object 5, all 
start conditions at fixed times of day are not 
active. 

The time is continuously updated by the de-
vice through its internal timers, but compo-
nent tolerances always result in a deviation 
from the actual time. Therefore, the current 
time should be sent to the device by a pre-
cise timer at least twice a day in order to 
keep the deviation as small as possible. 

Start after last trigger 
Here you can specify the time interval to wait after the 
previous activation before executing the step. This 
start condition is not available for step 1. 

Start time 

Here either the time day or the waiting time can be specified for 
the execution of the current step, if a timed start condition is 
used. 

Start by ON/OFF telegram 

When using this start condition, a separate object is available for 
each step: 

Group object 

Type KNX 

Size 

Direction 

GO 35-66 Dimmer A: Sequence Step x 
on/off - Switch 

1.001 

1 Bit 

From KNX 

 
An ON telegram to one of these objects activates the respective 
step, the sequence is then continued according to its configura-
tion from this step onwards. 

An OFF telegram also activates this step, but resets the se-
quence at the same time. 

Start by scene number 

When using this start condition, the following object becomes 
visible: 

Group object 

Type KNX 

Size 

Direction 

GO 31 Dimmer A: Sequence scene - 
Activate step 

18.001 

1 Byte 

From KNX 

 
A telegram with the set scene on this object activates the respec-
tive step, the sequence is then continued according to its config-
uration from this step onwards. 

All steps with this start condition are controlled by this object. 

Action 

When the step is activated, the configured function is executed, 
the following functions are available for selection: 

 

None 
No function is executed, for example this can be used 
to implement a switch-on delay for a sequence. 

 

Start loop 
The sequence continues from the selected step. Pa-
rameters for the initial step of the loop and the number 
of loops become visible. 

 

Send scene number 
When using this function, the following object becomes 
visible: 

Group object 

Type KNX 

Size 

Direction 

GO 32 Dimmer A: Se-
quence Scene - Send 
scene 

18.001 

1 Byte 

To KNX 

A parameter for the scene number to be sent becomes 
visible. When the step is activated, this scene number 
is sent via the object. 

All steps send the scene number via this object, if this 
function is used for the respective step. 

 

Brightness 
Parameters for brightness and fade time become visi-
ble. When this step is activated, the dimmer dims from 
the current brightness value to the specified brightness 
with the parameterized fade time. This time is related 
to a complete dimming process of 0-100%. 

K. 

Actuator B: General 

 

 

Name (30 Characters) 

An arbitrary name can be assigned for the channel. However, 
this should be clear and meaningful, this makes it easier to work 
with the associated group objects, because the given name is 
displayed there as a label. If no name is assigned, the group 
objects are named “Actuator B: …”. 

Function 

This parameter defines the functionality of the actuator.  

The following options are selectable: 

 

Disabled 

 

Switch dimmer 

 

Universal output 

 

On/Off delay 

 

Staircase function 

 

Valve actuator (PWM for thermal servo) 

If the actuator is not “Disabled”, the following parameters are 
displayed: 

Содержание 1D1O

Страница 1: ... Pressing button A long switches to manual operation of the dimming actuator channel channel A This is indicated by cyclic one time flashing of the LED Ch M in orange Pressing button B long switches to manual operation of the switching actuator channel channel B This is indicated by cyclic two time flashing of the LED Ch M in orange In manual operation the respective channel can be switched on by ...

Страница 2: ...stance of the output Between 0 and 100 the switching losses caused by the PWM are added Overall there is a maximum power loss in the upper dimming range The rated power of 144W refers to the maximum permitted ambient temperature for free installation If there are other devic es next to the dimming actuator that emit heat the power that can be connected is reduced Alternatively the devices can also...

Страница 3: ...e dimmer output switches off and an ON telegram is sent via the respective object The output is disabled for the duration of the error state if it is resolved the respective object sends an OFF telegram and the dimmer can be used normally again Overload is triggered from a load of 8A overtemperature from a measured temperature of 85 C in the load section If no value is received by the load section...

Страница 4: ...value scene slumber function or sequencer During manual override values of object 20 are ignored each manual override restarts the fallback time After the fallback time set in the parameter has elapsed the values received on object 20 are processed again Via object 19 the automatic can be switched on or off at any time it also serves as a state object for automatic mode Slumber function The slumbe...

Страница 5: ...ays visible values are used Dimming value on ON telegram night If the dimmer is in night mode this value is activated by ON telegram via object 11 and suitable parameterization Dimming value on OFF telegram night If the dimmer is in night mode this value is activated by OFF telegram via object 11 and suitable parameterization Fade time for day night switching This fade time is only active if switc...

Страница 6: ... of the dimmer Use brightness max value of red green blue The largest value of the 3 bytes is used to control the brightness of the dimmer Minimal value for changing color by object This parameter can be used to configure which minimum dim ming value can be set via object 14 If a value below the mini mum value is received the dimmer is controlled with the minimal value Maximal value for changing c...

Страница 7: ...dims to orientation light The period refers to a complete dimming pro cess of 0 100 Reaction on OFF telegram Here it can be set how the staircase function behaves in the event of an OFF telegram The following options are available Ignore No reaction of the channel on OFF telegram Switch off Switch to switch off value from the parameters Switch to switch off delay The delay time is started with OFF...

Страница 8: ...KNX Size Direction GO 18 Dimmer A Scene Activ Lrn 18 001 1 Byte From KNX Fade time on activation of scene Here the period can be set in which the received scene is dimmed to The period refers to a complete dimming process of 0 100 Scene 1 16 These parameters can be used to configure the reaction of the channel when the respective scene is received It is available No reaction Dimming value The outp...

Страница 9: ...rior dimming abs Set value 5 001 1 Byte From KNX If the lock was activated by object 22 other received telegrams for dimmer automatic mode slumber scene function and se quencer are not executed In addition to the lock object 3 priority objects become visible when the lock function is activated with which the dimmer can be controlled independently of the lock This makes it possible to set an initia...

Страница 10: ... On next activated step The sequence is continued with the next activated step the next step can be activated by object or time controlled Off time Only visible if the sequence is to be continued after off time with this parameter the off time can be configured Step after man operation This step is executed when resuming after manual operation the function of the set step is always executed regard...

Страница 11: ...t the same time Start by scene number When using this start condition the following object becomes visible Group object Type KNX Size Direction GO 31 Dimmer A Sequence scene Activate step 18 001 1 Byte From KNX A telegram with the set scene on this object activates the respec tive step the sequence is then continued according to its config uration from this step onwards All steps with this start c...

Страница 12: ...unctions Group object Type KNX Size Direction GO 75 Actuator B Lock Activate 1 001 1 Bit From KNX GO 76 Actuator B Prior output Switch 1 001 1 Bit From KNX Example of the priority object In the case of events in public buildings or in restaurants the normal operation can be set into an inoperative state by the lock group object Thus it is possible to lock during the lecture or concert switches tha...

Страница 13: ...lected on the parameter page Actuator B General delayed switching times can be con figured The Actuator B On Off Delay parameter page is displayed for this purpose Group object Type KNX Size Direction GO 71 Actuator B Output Switch 1 001 1 Bit From KNX N Actuator B On Off delay On delay time The duration of the switch on delay is configured in this parame ter Input 1 0 Output T 1 0 Off delay time ...

Страница 14: ...in Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enabled this is only trig gered if the value is permanently 0 or 100 On every other control value the servo already moves so there is no need for a stuck protection Control value 0 Open servo for the set time C...

Страница 15: ...nction type Timer The timer specific parameters and group objects are available Function type Logic The logic specific parameters and group objects are available These additional logic and timer functions can be linked to one another by means of the associated group objects This also allows to create complex structures For this purpose the output of a function is set to the same group address as t...

Страница 16: ... output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are switched off 0 Gate type XNOR gate The output is triggered on 1 if both inputs are equal Gate type INVERTER Input on 1 is converted into output off 0 Input off 0 is con verted into outp...

Отзывы: