J. 

Dimmer A: Sequencer 

 

The sequencer can be used to create complex sequence pro-
grams consisting of up to 32 individual steps for the dimmer 
channel. The individual steps can be activated under the follow-
ing starting conditions: 

 

At a fixed time of day 

 

After a waiting time from a previous step has elapsed 

 

By on/off telegram 

 

When receiving a parameterized scene number 

When a step is activated, a value can be dimmed to or a scene 
number can be sent, and a step or a whole sequence of steps 
can be repeated cyclically. 

The following objects are available for the general control of the 
sequencer: 

Group object 

Type KNX 

Size 

Direction 

GO 33 Dimmer A: Sequence suspend - 
Suspend/Resume 

1.001 

1 Bit 

From KNX 

GO 34 Dimmer A: Sequence on/off - 
Switch 

1.001 

1 Bit 

From KNX 

The following parameters determine the general behavior of the 
sequencer: 

Steps of sequencer 

Number of steps (0...32) to be used 

Resume sequence after man. operation 

An activated sequence can always be interrupted or continued 
via object 33 an ON telegram interrupts the sequence, and with 
an OFF telegram it is continued. 

A sequence is also interrupted after manual operation, i.e. after 
commands for dimmer, automatic mode, slumber or scene func-
tion. 

In addition, this parameter determines how an interrupted se-
quence can still be continued: 

 

Only by object 
The sequence can only be continued by object 33. 

 

After off-time 
The sequence is continued after the set off-time. 

 

On next activated step 
The sequence is continued with the next activated 
step, the next step can be activated by object or time-
controlled. 

Off-time 

Only visible if the sequence is to be continued after off-time, with 
this parameter the off-time can be configured. 

Step after man. operation 

This step is executed when resuming after manual operation, the 
function of the set step is always executed, regardless of its 
otherwise set starting conditions. 

P

olarity of object “Sequence on/off“ 

This parameter can be used to set the telegram value with which 
the sequence can be switched on and off via object 34. If the 
sequence is switched off, any further activation of a step is disa-
bled. 

Behavior on switching on 

Here it is determined how the sequencer behaves when 
switched on by object 34: 

 

No reaction 
No function is executed, the sequencer waits for steps 
to be activated. 

 

Step x 
The function of the step is executed (independent of 
the other set start conditions of the step), the se-
quence is then continued according to its configuration 
from this step onwards. 

Switching on also reactivates a sequence interrupted by manual 
operation. 

Behavior on switching off 

Here it is determined how the sequencer behaves when 
switched off by object 34: 

 

Complete actual step 
If the sequencer is in a dimming process, it is complet-
ed. 

 

Step x 
The function of the step is executed (independent of 
the other set start conditions of the step). 

 

Stop immediately 
If the sequencer is in a dimming process, it is stopped. 

Apart from the set behavior when switching off, any further acti-
vation of a step after switching off is disabled until the sequencer 
is switched on again by object 34. 

Step 1-32: 

 

Содержание 1D1O

Страница 1: ... Pressing button A long switches to manual operation of the dimming actuator channel channel A This is indicated by cyclic one time flashing of the LED Ch M in orange Pressing button B long switches to manual operation of the switching actuator channel channel B This is indicated by cyclic two time flashing of the LED Ch M in orange In manual operation the respective channel can be switched on by ...

Страница 2: ...stance of the output Between 0 and 100 the switching losses caused by the PWM are added Overall there is a maximum power loss in the upper dimming range The rated power of 144W refers to the maximum permitted ambient temperature for free installation If there are other devic es next to the dimming actuator that emit heat the power that can be connected is reduced Alternatively the devices can also...

Страница 3: ...e dimmer output switches off and an ON telegram is sent via the respective object The output is disabled for the duration of the error state if it is resolved the respective object sends an OFF telegram and the dimmer can be used normally again Overload is triggered from a load of 8A overtemperature from a measured temperature of 85 C in the load section If no value is received by the load section...

Страница 4: ...value scene slumber function or sequencer During manual override values of object 20 are ignored each manual override restarts the fallback time After the fallback time set in the parameter has elapsed the values received on object 20 are processed again Via object 19 the automatic can be switched on or off at any time it also serves as a state object for automatic mode Slumber function The slumbe...

Страница 5: ...ays visible values are used Dimming value on ON telegram night If the dimmer is in night mode this value is activated by ON telegram via object 11 and suitable parameterization Dimming value on OFF telegram night If the dimmer is in night mode this value is activated by OFF telegram via object 11 and suitable parameterization Fade time for day night switching This fade time is only active if switc...

Страница 6: ... of the dimmer Use brightness max value of red green blue The largest value of the 3 bytes is used to control the brightness of the dimmer Minimal value for changing color by object This parameter can be used to configure which minimum dim ming value can be set via object 14 If a value below the mini mum value is received the dimmer is controlled with the minimal value Maximal value for changing c...

Страница 7: ...dims to orientation light The period refers to a complete dimming pro cess of 0 100 Reaction on OFF telegram Here it can be set how the staircase function behaves in the event of an OFF telegram The following options are available Ignore No reaction of the channel on OFF telegram Switch off Switch to switch off value from the parameters Switch to switch off delay The delay time is started with OFF...

Страница 8: ...KNX Size Direction GO 18 Dimmer A Scene Activ Lrn 18 001 1 Byte From KNX Fade time on activation of scene Here the period can be set in which the received scene is dimmed to The period refers to a complete dimming process of 0 100 Scene 1 16 These parameters can be used to configure the reaction of the channel when the respective scene is received It is available No reaction Dimming value The outp...

Страница 9: ...rior dimming abs Set value 5 001 1 Byte From KNX If the lock was activated by object 22 other received telegrams for dimmer automatic mode slumber scene function and se quencer are not executed In addition to the lock object 3 priority objects become visible when the lock function is activated with which the dimmer can be controlled independently of the lock This makes it possible to set an initia...

Страница 10: ... On next activated step The sequence is continued with the next activated step the next step can be activated by object or time controlled Off time Only visible if the sequence is to be continued after off time with this parameter the off time can be configured Step after man operation This step is executed when resuming after manual operation the function of the set step is always executed regard...

Страница 11: ...t the same time Start by scene number When using this start condition the following object becomes visible Group object Type KNX Size Direction GO 31 Dimmer A Sequence scene Activate step 18 001 1 Byte From KNX A telegram with the set scene on this object activates the respec tive step the sequence is then continued according to its config uration from this step onwards All steps with this start c...

Страница 12: ...unctions Group object Type KNX Size Direction GO 75 Actuator B Lock Activate 1 001 1 Bit From KNX GO 76 Actuator B Prior output Switch 1 001 1 Bit From KNX Example of the priority object In the case of events in public buildings or in restaurants the normal operation can be set into an inoperative state by the lock group object Thus it is possible to lock during the lecture or concert switches tha...

Страница 13: ...lected on the parameter page Actuator B General delayed switching times can be con figured The Actuator B On Off Delay parameter page is displayed for this purpose Group object Type KNX Size Direction GO 71 Actuator B Output Switch 1 001 1 Bit From KNX N Actuator B On Off delay On delay time The duration of the switch on delay is configured in this parame ter Input 1 0 Output T 1 0 Off delay time ...

Страница 14: ...in Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enabled this is only trig gered if the value is permanently 0 or 100 On every other control value the servo already moves so there is no need for a stuck protection Control value 0 Open servo for the set time C...

Страница 15: ...nction type Timer The timer specific parameters and group objects are available Function type Logic The logic specific parameters and group objects are available These additional logic and timer functions can be linked to one another by means of the associated group objects This also allows to create complex structures For this purpose the output of a function is set to the same group address as t...

Страница 16: ... output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are switched off 0 Gate type XNOR gate The output is triggered on 1 if both inputs are equal Gate type INVERTER Input on 1 is converted into output off 0 Input off 0 is con verted into outp...

Отзывы: