63899-002 Rev. A 3/20/2024
52
If a jumper is used to check the switch, the jumper
MUST
be removed, and the Air
Proving Switch reconnected or an unsafe condition can occur resulting in
PERSONAL INJURY OR DEATH
E: COMBUSTION AIR BLOWER AND MOTOR
Cleaning of the combustion air blower is required if the blades show an accumulation of dust and lint,
or if the character of the flame indicates a deficiency of combustion air.
The motor and blower wheel are removed as one assembly. Locate the motor wires in the electrical
panel. Note the wire connection points in the terminal block and disconnect the motor wires from the
terminal block. Remove the two (2) bolts securing the motor to the burner housing.
Should removal of the blower wheel be necessary for cleaning or replacement of either it or the motor,
the blower wheel must be re-positioned correctly on the motor shaft. (Figure 20)
NOTE: DO NOT REMOVE BLOWER WHEEL FROM MOTOR SHAFT DURING
PERIODIC CLEANING.
Combustion Air Blower
Figure 20
F
. GAS PRESSURE SWITCHES
The gas pressure switches should never require maintenance. If nuisance problems persist, the
switches can be temporarily “jumped” out to bypass the switch’s function. If the burner functions
correctly, the switch has malfunctioned.
If a jumper is used to check the switch, the jumper
MUST
be removed, and the Air
Proving Switch reconnected, or an unsafe condition can occur resulting in
PERSONAL INJURY OR DEATH.
1/32”
FAN SPACING
Содержание LC2300M
Страница 35: ...63899 002 Rev A 3 20 2024 35 B WIRING DIAGRAM...
Страница 36: ...63899 002 Rev A 3 20 2024 36...
Страница 57: ...63899 002 Rev A 3 20 2024 57...
Страница 58: ...63899 002 Rev A 3 20 2024 58...
Страница 59: ...63899 002 Rev A 3 20 2024 59...
Страница 60: ...63899 002 Rev A 3 20 2024 60...
Страница 63: ...63899 002 Rev A 3 20 2024 63 This page intentionally left blank...