NOTE: IN MOST APPLICATIONS, VALVES AND DAMPERS CAN TYPICALLY ROTATE
PAST THE OPEN POSITION (90°) WITHOUT INTERFERENCE. THEREFORE, IT IS MOST
COMMON TO SET ALL ACTUATOR REFERENCE POSITIONS TO “OPEN”.
F.3 AZL DISPLAY
F.3-1 EXPLAINATION OF DISPLAY AND BUTTONS
AZL Unit
Figure 4
Button
Function
F (Fuel)
For adjusting the fuel actuator. (Keep 'F' pressed and adjust the actuator value by holding "+/-").
A (Air)
For adjusting the air actuator. (Keep 'A' pressed and adjust the actuator value by holding
“
+/-
“
).
A&F: VSD
For changing to parameter setting - mode P. (Press simultaneously
“
F&A
”
).
Info/Enter/Reset
For navigating through information or service mode; selecting (hold button for <1s), for
changing to a lower menu level (hold button for 1…3s), for
changing to a higher menu level (hold
button for 3…8s), for changing to operating menu (hold button for >8s). This button can be used
as an enter key in parameter setting mode and can be used as reset in the event of a fault.
Minus (-)
For decreasing the value. For navigating through curve adjustments during info and service
mode.
Plus (+)
For increasing the value. For navigating through curve adjustments during info and service
mode.
Plus & Minus:
ESC
No selection of value. (Hold
“
+/-
“
simultaneously).
Содержание LC2300M
Страница 35: ...63899 002 Rev A 3 20 2024 35 B WIRING DIAGRAM...
Страница 36: ...63899 002 Rev A 3 20 2024 36...
Страница 57: ...63899 002 Rev A 3 20 2024 57...
Страница 58: ...63899 002 Rev A 3 20 2024 58...
Страница 59: ...63899 002 Rev A 3 20 2024 59...
Страница 60: ...63899 002 Rev A 3 20 2024 60...
Страница 63: ...63899 002 Rev A 3 20 2024 63 This page intentionally left blank...
Страница 64: ...63899 002 Rev A 3 20 2024 64 NOTES...