
63899-002 Rev. A 3/20/2024
20
H.5 ELECTRICAL CONNECTIONS
:
The installation must be wired and grounded in accordance with local codes or in their absence,
with the National Electric Code ANSI/NFPA No. 70-2002 or latest edition.
In CANADA, all wiring shall be done in accordance with the Canadian Electrical Code.
H.6 SAFETY SYSTEM
The
safety system (Including hatches, doors, water levels, pressure, and temperature systems)
must be installed according to current regulations.
Power cables for the safety system must be
separated so incoming and outgoing signals do not cross within the same cable.
I. PRESSURE REGULATOR ADJUSTMENT
The pressure regulating gas valve (SKP25) is preset to 9 inches water column manifold pressure. This
may be field adjusted while the burner is in operation. Refer to Table 1 for pressure requirements.
When adjusting the (SKP25) regulator pressure according to that specified in Table 1, remove the
regulator cap for access to the slotted adjustment screw. Turning the screw counterclockwise reduces
burner inlet (manifold) pressure, clockwise increases the pressure. Reference Figure 9 for clarification.
SKP25 Regulating Gas Valve
Figure 9
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND
DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER
SERVICING.
IF ANY OF THE ORIGINAL BURNER WIRING MUST BE REPLACED,
IT MUST BE REPLACED WITH #18 AWG 105° C WIRE OR
EQUIVALENT.
Regulator Cap
Manifold
Pressure Test
Port
Содержание LC2300M
Страница 35: ...63899 002 Rev A 3 20 2024 35 B WIRING DIAGRAM...
Страница 36: ...63899 002 Rev A 3 20 2024 36...
Страница 57: ...63899 002 Rev A 3 20 2024 57...
Страница 58: ...63899 002 Rev A 3 20 2024 58...
Страница 59: ...63899 002 Rev A 3 20 2024 59...
Страница 60: ...63899 002 Rev A 3 20 2024 60...
Страница 63: ...63899 002 Rev A 3 20 2024 63 This page intentionally left blank...
Страница 64: ...63899 002 Rev A 3 20 2024 64 NOTES...