63899-002 Rev. A 3/20/2024
17
Table 2: LC2300M with 1 ½’ Gas Line - L.P. Gas
(Siemens VGD 1” Double Valve Body with SKP15 and SKP25 Regulators)
Firing
Rate
(1000’s
Btu/hr)
Combustion
Air Shutter
Setting (0-
90*)
Butterfly
Valve Gas
Actuator
Setting (0-
90*)
O
2
(%)
Manifold
Pressure
Inch of
Water
Minimum Inlet
Pressure
Inch of Water
(Burner Running)
Dimension
“A”
Setting
(Figure 6)
57
0
1.8
3-4
9
10
3-3.25”
110
0
4.0
3-4
9
10
3-3.25”
250
5
6.8
3-4
9
10
3-3.25”
550
26.5
12.1
3-4
9
10
3-3.25”
1000
42.5
17.5
3-4
9
10
3-3.25”
1400
57
20.9
3-4
9
10
3-3.25”
1800
68
23.5
3-4
9
10
3-3.25”
2000
82.5
26.8
3-4
9
10
3-3.25”
2300
90
30
3-4
9
10
3-3.25”
*For all firing rates above, a yellow spring, part # 1000176 (provided) is used.
NOTES ON TABLES:
•
Combustion Air Shutter Setting is the position of the air shutter from 0 to 90 degrees.
•
O
2
% is the percentage of oxygen measured in flue products.
•
Manifold Pressure is the gas pressure measured from the pressure tap on the back of the
SKP25 regulating gas valve. (Figure 8 ahead)
•
Minimum Inlet Pressure is the minimum gas supply pressure to the gas train necessary to
obtain the desired flow rate. Inlet supply pressures up to 48 in w.c. are permitted.
Содержание LC2300M
Страница 35: ...63899 002 Rev A 3 20 2024 35 B WIRING DIAGRAM...
Страница 36: ...63899 002 Rev A 3 20 2024 36...
Страница 57: ...63899 002 Rev A 3 20 2024 57...
Страница 58: ...63899 002 Rev A 3 20 2024 58...
Страница 59: ...63899 002 Rev A 3 20 2024 59...
Страница 60: ...63899 002 Rev A 3 20 2024 60...
Страница 63: ...63899 002 Rev A 3 20 2024 63 This page intentionally left blank...
Страница 64: ...63899 002 Rev A 3 20 2024 64 NOTES...