OMM-0153_E
• 5/11/2023 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 48 of 124
CENTURION Installation, Operation & Maintenance Manual
SECTION 5: INITIAL START-UP
Figure 5-8: Over-Temperature Limit Switches
5.4.1 Adjusting The Automatic Reset Limit Switch Temperature
1. Power unit ON and remove the front panel to expose the Over-Temperature Limit switches.
2. Press the
Automatic Reset Limit Switch’s SET button: SP appears in the display.
3. Press the SET button again. The current setting stored in memory is displayed.
4.
Press the ▲ or ▼ arrow buttons to change the display to the desired temperature setting.
5. When the desired temperature is displayed, press the SET button.
6.
Press both the SET and ▼ arrow buttons at the same time. This stores the setting in memory;
note that OUT1 appears in the upper-left corner of the display as confirmation.
Figure 5-9: Auto-Reset Over-Temperature Limit Switch
5.4.2 Resetting The Manual Reset Limit Switch
Perform the following steps to rest the Manual Reset Limit Switch after it has gone into Alarm
mode, and after the temperature has fallen at least 10 degrees below the limit.
1. Power unit
ON
and remove front panel to expose Over-Temperature Limit switches.
2.
Press the Manual Reset Limit Switch’s
RST
(Reset) button.
3. You can now restart the unit.
Figure 5-10: Manual Reset Over-Temperature Limit Switch