CENTURION Installation, Operation & Maintenance Manual
SECTION 1: SAFETY PRECAUTIONS
1.4 Important
– Requirements for Massachusetts Installations
……………….[Extracted Information From 248 CMR 5.08 (2) ]…………………
Installations within the Commonwealth of Massachusetts must conform to the following requirements:
•
Water Heater must be installed by a plumber or a gas fitter licensed within the Commonwealth of Massachusetts.
•
Prior to operation, the complete gas train and all connections must be leak tested using a non-corrosive soap.
•
The vent termination must be located a minimum of 4 feet above grade level. If side-wall venting is used, the
installation must conform to the following requirements
extracted from 248 CMR 5.08 (2):
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used
in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where
the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS:
At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard-wired carbon monoxide
detector with alarm and battery back-up is installed on the floor level where the gas equipment is to be installed.
In addition, the installing plumber or gasfitter shall observe that a battery operated or hard-wired carbon
monoxide detector with alarm is installed on each additional level of the dwelling, building or structure served by
the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure
the services of qualified licensed professionals for the installation of hard-wired carbon monoxide detectors.
a.
In the event the side wall horizontally vented gas fueled equipment is installed in a crawl space or attic the
hard-wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor.
b.
In the event that the requirements of this subdivision cannot be met at the time of completion of installation,
the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that
during said thirty (30) day period, a battery-operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS:
Each carbon monoxide detector as required in
accordance with
the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE:
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at
a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch
in size,
"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION:
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Section 10 entitled "Equipment Not Required to Be Vented" in the most current edition
of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of
Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system
components with the equipment, the instructions provided by the manufacturer for installation of the equipment
and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the
parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be
satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment
installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the completion of the installation.
……………….[End of Extracted Information From 248 CMR 5.08 (2)]…………………