Operation and Maintenance
L-OMM-0003_A
• 10/8/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
114
of
157
You can setup the operation of the system by pressing the
System
button. To setup operation
of the system, continue with the system setup.
NOTE:
Mixed Setback Offset is only available if a schedule is selected.
12.2.4 Selecting and Setting the Outlet Water Temperature Setpoint:
W A R N I N G !
BEFORE setting mixed outlet water temperature or electing default temperature, point-of-use
mixing valves and/or temperature limiting devices MUST be installed at all fixtures (faucets,
sinks, tubs, showers, etc.)
Set the safe, appropriate and desired outlet water
temperature for your users, application and facility
by pressing
Mixed Outlet Setpoint
on the
System Setup menu and then using the
SLIDER
or
UP
and
DOWN
arrows until the selected
temperature is displayed. Press
Accept
.
W A R N I N G
The owner or manager of the water distribution system is solely responsible for determining
the safe and appropriate temperatures to protect people using, contacting or exposed to water
or any parts of the water distribution system from scalding, burning, thermal shock or other
hazards, and to control water-borne bacteria in the system.
Once the desired temperature is selected, press the
Accept
icon to apply the setting. The
System Setup screen reappears.
NOTE:
The setpoint is controlled by the Edge SC controller. Expect the setpoint to be reset
and changed based on Edge SC programming after any local changes at the controller.
To turn on the
Mixed Setback Offset
feature (sets
temperature lower during unoccupied period), press
On
and
Accept.
Change the temperature using the
slider
or by pressing the
UP
or
DOWN
arrows, then
press
Accept
when done.