Element
Section 10: Edge SC Controller Operation
L-OMM-0003_A
• 10/8/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
85
of
157
The Element
’s mixed output compensates for this rise in temperature, so the temperature will be
controlled to the mixed output setpoint and control limits once reaching steady state.
Figure 62 - Sanitation Loop
A confirmation screen will display to review the settings provided. Adding a comment to the
process will included it in the generated event.
10.3.9.3
Full System Thermal Sanitation
The
Thermal Sanitation
screen shows the current status and allows the user to start a Thermal
Sanitation or Add More Time.
It is recommended to include full system thermal sanitation cycles and regular testing for
Legionella
in your building’s Water Management Plan, in compliance with ASHRAE 188.
10.3.10 Monitoring
Most components allow information to be monitored through the
Monitoring
tab of each menu.
The
Monitoring
menu records previous variables and allows users to view previous
temperatures from various timeframes.