52
INTELLIZONE2 INSTALLATION MANUAL
SVH Blower Performance Data
Variable Speed ECM
Model
Max ESP Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7 Speed 8 Speed 9 Speed 10 Speed 11 Speed 12
033 0.75
250
400 G
550 L
650
750
850
1000
1150
1250 H 1350 Aux
1450
1600
042
0.75
250
450 G
650 L
800
950
1050
1200
1350
1450
1600 H
1750 Aux
1850
050
0.75
300
550 G
800 L
1000
1150
1300
1450
1600
1750
1900 H 2050 Aux
2200
**VS
Compressor
Speed
1-2
3-4
5-6
7-8
9-10
11-12
4/15/2020
** VS Compressor speed is given for the factory default cfm settings. When the cfm default settings are changed it will change
the relationship to the compressor speed that is shown in the table. In cooling mode compressor speeds 10-12 are only available
when SuperBoost mode is selected at the thermostat.
Factory settings are at recommended G, L , H and Aux positions
“G” may be located anywhere within the airflow table.
“L” setting should be located within the boldface CFM range
“H” setting MUST be located within the shaded CFM range
“Aux” setting MUST be equal to or higher than factory setting shown in the table above
CFM is controlled within 5% up to the maximum ESP