INTELLIZONE2 INSTALLATION MANUAL
Blower Data - Package Unit cont.
Cooling Airflow Selection (Variable Speed)
Selected in AID Tool
From IZ2
Air Level %
Actual
Blower Speed*
AID Reported
Blower Speed
Cont Blower
Low Comp
Hi Comp
Aux Heat
1
2
Comp Speeds
1 & 2
Low Selection
25%
Blower Spd 3 - 15%
3
--->
Comp Speeds
3 & 4
40%
Blower Spd 4 - 15%
4
Comp Speeds
5 & 6
55%
Blower Spd 5 - 15%
5
Comp Speeds
7 & 8
70%
Blower Spd 6 - 15%
6
Comp Speeds
9 &10
Cooling Max
85%
Blower Spd 7 - 15%
7
Comp Speeds
11 & 12
SuperBoost Only
100%
Blower Spd 8 - 15%
8
--->
--->
9
10
11
--->
12
NOTE:
* Denotes default cooling airflow setting of 15% less than heating mode airflow.
Dual or Single Capacity
Heating Unit
Call
Blower Level Call
(Norm)
Blower Level Call
(Dehumid)
H1
55 or 70%
na
H2
85 or 100%
na
H2, W
Aux Blower
na
W
Aux Blower
na
G
G Only (cont Blower)
na
Cooling Unit
Call
Blower Level Call
(Norm)
Blower Level Call
(Dehumid)
C1
55 or 70%
55 or 70% less 15% cfm
C2
85 or 100%
85 or 100% less 15% cfm
G
G Only (cont Blower)
G Only (cont Blower)
Variable Speed Capacity
Heating Unit
Call
Blower Level Call
(Normal Staging
Shown)
Blower Level Call
(Dehumid)
H1 or H2
25% or 40%
na
H3 or H4
25% or 40% or 55%
na
H5 or H6
40% or 55% or 70%
na
H7 or H8
55% or 70% or 85%
na
H9 or H10
70% or 85% or 100%
na
H11 or H12
85% or 100%
na
H9-H12, W
Aux Blower
na
W
Aux Blower
na
G
G Only (cont Blower)
na
Cooling Unit
Call
Blower Level Call
(norm)
Blower Level Call
(Dehumid)
C1 or C2
25% or 40%
Norm less 15% cfm
C3 or C4
25% or 40% or 55%
Norm less 15% cfm
C5 or C6
40% or 55% or 70%
Norm less 15% cfm
C7 or C8
55% or 70% or 85%
Norm less 15% cfm
C9 or C10
70% or 85% or 100%
Norm less 15% cfm
C11 or C12
85% or 100%
Norm less 15% cfm
G
G Only (cont Blower)
G Only (cont Blower)
NOTE:
C10-C12 are only available in SuperBoost mode.
In cooling a similar procedure occurs with the exception
that compressor speed is limited to a maximum of speed
9. However compressor speed 10-12 is available for a
short period of time and the resulting airflow during the
‘SuperBoost’ mode is shown below. Another exception is
when dehumidification reduces airflow; it is a reduction
as shown below. Therefore, in dehumidification mode, if
blower speed 3 is selected, the resulting airflow will be
blower speed 3, less 15%.