19
INTELLIZONE2 INSTALLATION MANUAL
IntelliZone2 Confi guration cont.
Equipment and Number of Zones
The first screen is Equipment and # of Zones. Here the
total number of desired zones and the type of equipment
is selected. Equipment is automatically detected. Press
the up and down arrows until the desired number of
zones appears.
The zones should always be installed
sequentially starting with the MasterStat always in Zone 1.
•
Single speed equipment is limited to a maximum of
2 zones
•
Dual Capacity equipment is limited to a maximum of
4 zones
•
Variable speed equipment can have up to the
maximum of 6 zones.
NOTE:
If the number of zones selected is less than 6, the
remaining zones will be disabled.
MasterStat Configuration
Once added to the Aurora system, the setup and
configuration mode should be entered at the MasterStat
by holding a finger over the IntelliZone2 logo for 5 sec. The
Configuration and Setup mode will appear automatically.
NOTE:
These options are intended to be used by the installer.
End users are not advised to change or modify any of these
settings. Doing so may make your equipment stop working
properly and/or may void the warranty of the zoning system
as well as the equipment connected to the thermostat.
It should be noted that the MasterStat Z2TK troubleshooting
harness can be useful during setup by allowing the temporary
connection of the MasterStat directly at the IntelliZone2 relay
board for ease of configuration or servicing.
P3
–
M
as
te
rS
ta
t L
oc
al
C
B-
A+
R
Z2
TK
K
it
IntelliZone2
Relay Panel
Use the Z2TK Harness to temporarily connect the IntelliZone2 MasterStat
directly to the IntelliZone2 Relay Panel for ease of setup or troubleshooting.
Damper
The Damper screen allows the selection of either 2 wire
(spring open) or 3 wire (power open/power closed) type.