29
INTELLIZONE2 INSTALLATION MANUAL
It should be noted that the MasterStat Z2TK
troubleshooting harness can be useful during startup
by allowing the temporary connection of the MasterStat
directly at the IntelliZone2 relay board for ease of
configuration or servicing.
Before powering the unit, check the following:
•
Fuses, breakers and wire size are correct.
•
Low voltage wiring has been completed.
•
MasterStat has been configured correctly.
•
Thermostats are wired and DIP switches are set for
proper zone #.
•
Blower speed has been set on the AID Tool.
•
Aurora control is configured for IntelliZone2.
System Startup and Checkout
Damper Open -
CCW
Damper Closed -
CW
Shaft End Position Indicator
Manual
Release
Button
Rotate by hand
Figure 25: Checking the Shaft Position Indicator
IntelliZone2 CFM Design
Damper and Continuous Blower Checkout
1.
Push the “Fan” button to the ON position on all
thermostats. (alternate method shown in the
note below)
2.
All dampers should start to open immediately.
3.
The blower should come on continuous fan speed. The
green zone LED’s flash while the dampers are opening,
once completely open the green LED will be solid ON.
The amber LED will illuminate to indicate fan ON.
4.
After approximately 100 seconds, all IntelliZone2
dampers should be completely opened. Check the
shaft position indicator on all damper actuators as
shown in Figure 25.
5.
Push the “Fan” button to the OFF position on
all thermostats.
6.
The blower and the amber LED should cycle off.
7.
All dampers should start to close immediately. After
approximately 100 seconds, all dampers should be
completely closed. Check the shaft position indicator
on all damper actuators shown in Figure 25.
NOTES:
To cycle dampers open and closed, access the
‘Test Mode’ Screen in the Installer Setup mode on the
IntelliZone2 MasterStat. Once here each damper can be
cycled individually by pushing the specific zone damper
button to check for proper operation. “Central Zone” mode
can also be used to open all dampers.
(3-wire PO/PC actuator shown)
IntelliZone2 CFM Design
Model
Max
CFM
Zone Design
CFM
CFM
Percentage
NS030
1000
700
50
NS036
1200
850
50
NS042
1300
900
50
NS048
1500
1000
50
NS060
1800
1100
50
NS070
2000
1100
50
ND026
800
600
40
ND038
1200
600
40
ND049
1500
800
40
ND064
1800
950
40
ND072
2000
1100
40
NV036/033
1500
300
20
NV048/042
1800
450
20
NV060/050
2100
450
20