13
INTELLIZONE2 INSTALLATION MANUAL
Thermostat Installation cont.
Mounting and Wiring the Thermostats
Position the thermostat subbase against the wall so that
it is level and the thermostat wires protrude through the
middle of the subbase. Mark the position of the subbase
mounting holes and drill holes with a 3/16-inch bit.
Install supplied anchors and secure base to the wall. Use
4-conductor 18 or 20 AWG thermostat wire unless issues
with EMI are anticipated. In that situation, use 24 AWG
shielded twisted pair cable grounded to “C” terminal on
the relay board end. Strip the wires back 1/4 inch (longer
strip lengths may cause shorts) and insert the thermostat
wires into the IntelliZone2 connector as shown in Figure
19. Tighten the screws to ensure tight connections. The
thermostat has the same type connectors, requiring the
same wiring. Caulk the hole in the wall where the wires
enter the thermostat.
NOTE:
See the instructions enclosed in the thermostat for
detailed installation and operation information.
Cleaning the Thermostat Display
Lightly dampen a clean non-abrasive cloth with water or
any non-abrasive household cleaner. To clean, gently wipe
the surface of the thermostat.
NOTE
: Do not spray liquids directly on the thermostat.
Figure 19: Wiring the Thermostat to the IntelliZone2
A+
R
C
B-
P14 – Zone 4
A+
R
C
B-
P15 – Zone 5
A+
R
C
B-
Zone 4 Stat
On
3
2
1
Zone 4 code shown
A+
R
C
B-
Zone 5 Stat
On
3
2
1
Zone 5 code shown
ZoneStat
SensorStat
Zone ID must be set for each Zone 2-6. ID can be
confirmed on ZoneStat by pressing cancel button for
5 sec. ID shown on display. See Zone ID Codes.
Zone ID must be set for each Zone 2-6. ID cannot be
confirmed on Zone SensorStat. See Zone ID Codes.
Relay Board
A+
R
C
B-
P1
1 – Zone 1
MasterStat
DX+
R
C
DX-
Zone 1
MasterStat
MasterStat is
always Zone 1
S1
S2
IntelliZone2
Relay Board
A+
R
C
B-
P1
6 – Zone 6
DX+
R
C
DX-
S1
S2
Optional
Remote
Sensor
IntelliZone2
Relay Board
MasterStat
TPCC32U01
On
3
2
1
On
3
2
1
On
3
2
1
Zone 4
Zone 5
Zone 3
On
3
2
1
Zone 2
On
3
2
1
Zone 6
Zone ID Codes
NOTES:
1) Zone ID must be set for each Zone 2-6. ID can be confirmed on ZoneStat
by pressing cancel button for 5 sec. ID shown on display.
2) Small screw driver can be used to set ID thru protective plastic skin!
3) MasterStat always Zone 1. Zone ID not necessary.
4) TPCC32U01 zone is set through its touchscreen.
(Note 4)
Optional