15
INTELLIZONE2 INSTALLATION MANUAL
A+
R
C
B-
P14 – Zone 4
A+
R
C
B-
P15 – Zone 5
A+
R
C
B-
Zone 4 Stat
On
3
2
1
Zone 4 code shown
A+
R
C
B-
Zone 5 Stat
On
3
2
1
Zone 5 code shown
ZoneStat
SensorStat
Zone ID must be set for each Zone 2-6. ID can be
confirmed on ZoneStat by pressing cancel button for
5 sec. ID shown on display. See Zone ID Codes.
Zone ID must be set for each Zone 2-6. ID cannot be
confirmed on Zone SensorStat. See Zone ID Codes.
Relay Board
A+
R
C
B-
P1
6 – Zone 6
DX+
R
C
DX-
S1
S2
Optional
Remote
Sensor
IntelliZone2
Relay Board
TPCC32U01
On
3
2
1
On
3
2
1
On
3
2
1
Zone 4
Zone 5
Zone 3
On
3
2
1
Zone 2
On
3
2
1
Zone 6
Zone ID Codes
NOTES:
1) Zone ID must be set for each Zone 2-6. ID can be confirmed on ZoneStat
by pressing cancel button for 5 sec. ID shown on display.
2) Small screw driver can be used to set ID thru protective plastic skin!
3) MasterStat always Zone 1. Zone ID not necessary.
4) TPCC32U01 zone is set through its touchscreen.
(Note 4)
IntelliZone2 Confi guration cont.
Dual Fuel (Single Speed/Dual Capacity)
- When Dual Fuel
is selected for ‘Thermostat Type’ and a ‘W’ call is present
operation will be as follows:
1.
The temperature will be controlled by the MasterStat
while other zones are ignored.
2.
All zone dampers will open, Y1, Y2, G, W outputs shall
run for 60 seconds. After 60 seconds Y1 and Y2 will be
dropped and output only W and G (if Fan with Heat
Option is selected otherwise G will be dropped).
3.
There will be a two minute minimum run time once
Dual Fuel operation has been entered, regardless if
MasterStat heat call has been satisfied.
4.
Once the two minute minimum run time expires and
the ‘W’ call is satisfied at the MasterStat then Dual Fuel
operation will be terminated. There will be no down
staging.
5.
Once Dual Fuel operation is terminated all zone
dampers will close.
6.
There will be a 4 minute time delay once Dual Fuel
operation is terminated before compressor operation
for cooling or heating may begin
.
Dual Fuel (Variable Speed not applicable with 7 Series
Indoor Split)
- When Dual Fuel is selected for ‘Thermostat
Type’ and a ‘W’ call is present operation will be as follows.
1.
The temperature will be controlled by the MasterStat
while other zones are ignored.
2.
All zone dampers will open, the current compressor
speed, G and W outputs shall run for 60 seconds. After
60 seconds the compressor will be stopped and output
only W and G (if Fan with Heat Option is selected
otherwise G will be dropped).
3.
There will be a two minute minimum run time once
Dual Fuel operation has been entered, regardless if
MasterStat heat call has been satisfied.
4.
Once the two minute minimum run time expires and the ‘W’
call is satisfied at the MasterStat then Dual Fuel operation
will be terminated. There will be no down staging.
5.
Once Dual Fuel operation is terminated all zone
dampers will close.
6.
There will be a 4 minute time delay once Dual Fuel
operation is terminated before compressor operation
for cooling or heating may begin.
Fan with Heat Option (Dual Fuel Applications)
- Options
are ON or OFF. This selection determines whether G (fan)
output is to be ON or OFF when W (auxiliary heat) output
is ON.
Thermostat Type
NORMAL/DUAL FUEL
Normal - used for normal operation
Dual Fuel - used on dual fuel systems; needs
outdoor sensor to lockout dual fuel
ZoneStats/SensorStats PCB
MasterStat Configuration