1.13 Frost Protection (Ice Protection function)
Ice Protection function works to reduce the risk of freezing and thereby protect the fabric of the
boiler if either the CH Flow or CH Return temperature falls below 5°C. The ice protection
function will force the appliance to operate until the CH Flow temperature rises above 30°C.
This mode operates even when all timeclocks are set to ‘OFF’, and also if the control panel is
set to the ‘OFF’ mode using the Mode button (3).
Be aware of unexpected firing in these conditions.
The boiler must have a permanent live AC supply and an adequate fuel supply for the function
to operate.
When the function is operating ‘ICEP’ is displayed on the LCD.
1.14 Circulating Pump and Diverter Valve Exercise Functions
If the boiler has not operated the circulating pump or the diverting valve for a period of 24 hours,
it will operate these components for 10 seconds to prevent locking.
The boiler must have a permanent live AC supply for this function to operate.
1.15 Speed adjustment of the circulating pump
1.15.1 Combination Boilers
The speed of the circulating pump is controlled in both CH and DH modes by a signal from the
control panel. If the maximum speeds need to be adjusted to suit site conditions, refer to
Engineer Parameters in Section 11.7.1. The settings on the circulating pump must not be
adjusted from the factory default of PWM Profile A (heating).
1.15.2 Pumped and System Boilers
The speed of the circulating pump can be adjusted using the pushbutton and LED indications
on the pump. Please refer to the manufacturer’s documentation which is available via
www.warmflow.co.uk/support/downloads.
2500 Overs
WAR139220 Agentis Boiler Manual
Sig
3 Back
Содержание Agentis Series
Страница 2: ......
Страница 30: ...Page 29 4 5 Components 4 5 1 B Series Boilerhouse Casing Key Components...
Страница 31: ...Page 30 4 5 2 I Series Internal Casing 21 26 33 Models 44 Models...
Страница 32: ...Page 31 4 5 3 I Series Internal Key Components 21 26 33 Models 44 Models...
Страница 33: ...Page 32 4 5 4 I Series Internal Pump Group 21 26 33 Models 44 Models...
Страница 34: ...Page 33 4 5 5 I Series Internal System Components SK3 4 5 6 I Series Internal Combination Boiler Key Components...
Страница 35: ...Page 34 4 5 7 E Series External Casing 21 26 33 Models 44 Models...
Страница 36: ...Page 35 4 5 8 E Series External Key Components 21 26 33 Models 44 Models...
Страница 37: ...Page 36 4 5 9 E Series External Pump Group 21 26 33 Models 44 Models...
Страница 39: ...Page 38 4 5 12 Combination Boiler Pipe Layout...
Страница 41: ...Page 40 5 1 2 I Series Internal I21 I26 I33 5 1 3 I Series Internal I44...
Страница 42: ...Page 41 5 1 4 I Series Internal Combination Boilers I21C I26C I33C 5 1 5 E Series External E21 E26 E33...
Страница 43: ...Page 42 5 1 6 E Series External Base Tray E21 E26 E33 5 1 7 E Series External E44...
Страница 44: ...Page 43 5 1 8 E Series External E44 Base Tray 5 1 9 E Series External Combination Boilers E21C E26C E33C...
Страница 45: ...Page 44 5 1 10 E Series External Combination Boiler Base Tray E21C E26C E33C...
Страница 60: ...Page 59 6 3 2 Wiring Diagram Fuses The appliance must have a permanent live supply connected to operate...
Страница 61: ...Page 60 6 3 3 External 230V Two Channel Programmer Room Thermostat Optional Outdoor sensor...
Страница 62: ...Page 61 6 3 4 Internal Two Channel Programmer and Room Thermostat Optional Outdoor Sensor...
Страница 73: ...Page 72 6 6 9 Honeywell Y Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 74: ...Page 73 6 6 10 Honeywell S Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 93: ...Page 92 Kabin Pak External Plume Management Kit KPMK The kit comprises...
Страница 107: ...Page 106 11 4 Burner Start Up Cycle Lock out is indicated by a lamp on the control box...
Страница 122: ...Page 121 14 SPARES 14 1 RDB 2 2 BX Spares...
Страница 124: ...Page 123 14 2 RDB 3 2 BX Spares...
Страница 134: ...Page 133 Intentionally left blank...
Страница 135: ......