10.2.3 Combination Boiler Filling
Filling mode provides a facility to assist in removing air from the system during system filling.
The Filling mode is activated by simultaneously pressing the DHW- (2) and CH- button (6) for 10
seconds. The appliance must not be in ‘OFF’ mode.
During this function:
1. All heat demands are disabled
2. The circulating pump operates at the maximum speed
3. The diverter valve is moved to mid position
During this function, ‘FILL’ is shown on the LCD:
The function can be disabled by pressing the Mode button (3) for 5 seconds.
Alternatively the function is automatically stopped after a timeout period of 15 minutes. A
countdown timer is shown on the auxiliary digits.
10.2.4 System Pressure
Water loss from the system as indicated by a reduction in pressure on the pressure gauge may
be made up through the filling loop. In the first week of operation it is normal to see a drop in
system pressure. After this time the system pressure must be rechecked and the system
refilled. Failure to do so may lead to boiler faults.
Special attention must be given to the concentration of corrosion inhibitors in the system water
where there is a need for topping up or refilling. Inhibitor concentrations must be restored to the
concentrations specified by the inhibitor manufacturer.
Frequent or routine refilling and topping up of the system should not be necessary on an
ongoing basis and may prove harmful to the appliance. Should topping up prove necessary on a
frequent or routine basis you must contact Warmflow or your installer.
Содержание Agentis Series
Страница 2: ......
Страница 30: ...Page 29 4 5 Components 4 5 1 B Series Boilerhouse Casing Key Components...
Страница 31: ...Page 30 4 5 2 I Series Internal Casing 21 26 33 Models 44 Models...
Страница 32: ...Page 31 4 5 3 I Series Internal Key Components 21 26 33 Models 44 Models...
Страница 33: ...Page 32 4 5 4 I Series Internal Pump Group 21 26 33 Models 44 Models...
Страница 34: ...Page 33 4 5 5 I Series Internal System Components SK3 4 5 6 I Series Internal Combination Boiler Key Components...
Страница 35: ...Page 34 4 5 7 E Series External Casing 21 26 33 Models 44 Models...
Страница 36: ...Page 35 4 5 8 E Series External Key Components 21 26 33 Models 44 Models...
Страница 37: ...Page 36 4 5 9 E Series External Pump Group 21 26 33 Models 44 Models...
Страница 39: ...Page 38 4 5 12 Combination Boiler Pipe Layout...
Страница 41: ...Page 40 5 1 2 I Series Internal I21 I26 I33 5 1 3 I Series Internal I44...
Страница 42: ...Page 41 5 1 4 I Series Internal Combination Boilers I21C I26C I33C 5 1 5 E Series External E21 E26 E33...
Страница 43: ...Page 42 5 1 6 E Series External Base Tray E21 E26 E33 5 1 7 E Series External E44...
Страница 44: ...Page 43 5 1 8 E Series External E44 Base Tray 5 1 9 E Series External Combination Boilers E21C E26C E33C...
Страница 45: ...Page 44 5 1 10 E Series External Combination Boiler Base Tray E21C E26C E33C...
Страница 60: ...Page 59 6 3 2 Wiring Diagram Fuses The appliance must have a permanent live supply connected to operate...
Страница 61: ...Page 60 6 3 3 External 230V Two Channel Programmer Room Thermostat Optional Outdoor sensor...
Страница 62: ...Page 61 6 3 4 Internal Two Channel Programmer and Room Thermostat Optional Outdoor Sensor...
Страница 73: ...Page 72 6 6 9 Honeywell Y Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 74: ...Page 73 6 6 10 Honeywell S Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 93: ...Page 92 Kabin Pak External Plume Management Kit KPMK The kit comprises...
Страница 107: ...Page 106 11 4 Burner Start Up Cycle Lock out is indicated by a lamp on the control box...
Страница 122: ...Page 121 14 SPARES 14 1 RDB 2 2 BX Spares...
Страница 124: ...Page 123 14 2 RDB 3 2 BX Spares...
Страница 134: ...Page 133 Intentionally left blank...
Страница 135: ......