232
•
Fieldbus Communication
MODBUS
Functions
WAGO-I/O-SYSTEM
750
BACnet/IP Controller
Address Access
Length
(word)
Remark
0x1029 R
9
MODBUS-TCP
statistics
0x102A R
1
Number of TCP connections
0x1030 R/W
1
Configuration MODBUS/TCP Timeout
0x1031 W
1
Read out the MAC-ID of the controller
0x1050 R
3
Diagnosis of the connected I/O Modules
0x2000 R
1
Constant
0x0000
0x2001 R
1
Constant
0xFFFF
0x2002 R
1
Constant
0x1234
0x2003 R
1
Constant
0xAAAA
0x2004 R
1
Constant
0x5555
0x2005 R
1
Constant
0x7FFF
0x2006 R
1
Constant
0x8000
0x2007 R
1
Constant
0x3FFF
0x2008 R
1
Constant
0x4000
0x2010 R
1
Firmware
version
0x2011 R
1
Series
code
0x2012 R
1
Controller
code
0x2013 R
1
Firmware versions major revision
0x2014 R
1
Firmware versions minor revision
0x2020 R
16
Short description controller
0x2021 R
8
Compile time of the firmware
0x2022 R
8
Compile date of the firmware
0x2023 R
32
Indication of the firmware loader
0x2030 R
65
Description of the connected busmodules (module 0–64)
0x2031 R
64
Description of the connected busmodules (module 65-128)
0x2032 R
64
Description of the connected busmodules (module 129-192)
0x2033 R
63
Description of the connected busmodules (module 193-255)
0x2040 W
1
Software reset (Write sequence 0x55AA or 0xAA55)
0x2041 W
1
Format
Flash-Disk
0x2042 W
1
Extract HTML sides from the firmware
0x2043 W
1
Factory
Settings
Содержание 750-830