BACnet/IP Controller 750-830
•
107
Programming the PFC Using WAGO-I/O-PRO CAA
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
ETHERNET
Over the "Ethernet" link, you will reach a website on which you can configure
the bandwidth limit and transmission rate for ETHERNET communication.
With the BACnet/IP Controller, you will use Port 1 while setting the transmis-
sion rate ("Speed Configuration") (see Tab. 3-20).
Tab. 3-20: Set transmission rate ("Speed Configuration“)
Parameter
Description
Enable Port
Deactivates the ETHERNET port. Both ports cannot be deac-
tivated at the same time.
Enable Power-Save Mode Activates the energy saving mode for the ETHERNET port
Enable Auto MDI-X
Activates the Auto MDI-X function of the ETHERNET port.
The "Auto MDI-X" function employs an internal switching
functionality to allow the use of either crossed (Crossover) or
straight-in (Patch) cables.
Enable Autonegotiation
Activates the autonegotiation function of the ETHERNET
port. The "Autonegotiation" function enables automatic de-
termining (negotiating) of the best-possible baud rate and the
optimal transfer mode between two link partners.
10 MBit Half Duplex
Configures the ETHERNET port for a baud rate of 10 MBit,
with a half duplex transfer mode.
10 MBit Full Duplex
Configures the ETHERNET port for a baud rate of 10 MBit,
with a full duplex transfer mode.
100 MBit Half Duplex
Configures the ETHERNET port for a baud rate of 100 MBit,
with a half duplex transfer mode.
100 MBit Full Duplex
Configures the ETHERNET port for a baud rate of 100 MBit,
with a full duplex transfer mode.
Enable IEEE 802.3x
Full Duplex Flow Control
Activates automatic flow control for the full duplex transfer
mode
A bandwidth limit function can also be configured for the ETHERNET port.
The following modes can be configured under Section "Bandwidth/Sniffer
Configuration" in the option fields "Limit mode":
Mode
Description
ALL
All ETHERNET data packets are limited
BC MC FU Broadcast, multicast and flooded-unicast data packets are limited
BC MC
Broadcast and multicast data packets are limited
BC
Broadcast data packets are limited