BACnet/IP Controller 750-830 • 151
BACnet Building Controller (B-BC)
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
3.1.12.2.1 Analog Input Object
The Analog Input object defines a standardized object whose properties repre-
sent the externally visible characteristics of an analog input.
The Analog Input Object and its properties are summarized in Tab. 3-28. The
properties are described in section
.
Tab. 3-28: Properties of the Analog Input Object
Property
Data Type
Default Value
Writable via BACnet by
means of
BACnetObjectIdentifier
-
-
CharacterString
Analog_Input_X
-
BACnetObjectType ANALOG_INPUT
-
REAL
-
-
CharacterString
*see
footnote
WriteProperty
'
'
WriteProperty
BACnetStatusFlags '000' -
BACnetEventState State_Normal (0)
-
BACnetReliability 0 WriteProperty
'0'
-
Unsigned
0
-
BACnetEngineeringUnits
NO_UNITS
(95)
WriteProperty
0
-
0
-
REAL
0 -
REAL
0
WriteProperty
0
WriteProperty
Unsigned
0
WriteProperty
REAL
0
WriteProperty
REAL
0
WriteProperty
REAL
0 WriteProperty
BACnetLimitEnable '111' WriteProperty
BACnetEventTransitionBits
'111' WriteProperty
BACnetEventTransitionBits '111'
-
BACnetNotifyType Alarm
(0)
WriteProperty
BACnetARRAY[3] for BACnet-
TimeStamp
UNSPECIFIED -
*corresponds to the item number of the module