86 •
BACnet/IP Controller 750-830
Fieldbus Node Start-up
WAGO-I/O-SYSTEM
750
BACnet/IP Controller
Note
To address additional fieldbus nodes, enter a similar text line for each node,
with your own specific data.
8. In the menu
File
select the menu item
Save
to store the changed settings in
the "bootptab.txt" file.
9. Close the editor.
3.1.7.2.4.2 BootP
Server
1. On your PC, go to
Start
and select the menu item
Programs \ WAGO
Software \ WAGO BootP Server
.
2. Click on WAGO BootP server to open the dialog window.
3. Click on Start in the dialog window that then appears. This activates the
query/response mechanism of the BootP protocol.
A number of messages are then output at the BootP server. Error messages in-
dicate that some services (such as Port 67, Port 68) are not defined in the op-
erating system.
Fig. 3-13: Dialog window for the WAGO-BootP Server, with messages
P012909d
4. To close the BootP server again, click
Stop
and then click the button
Exit
.