296 • List of all BACnet Properties in Native Operation
Object_Identifier
WAGO-I/O-SYSTEM
750
BACnet/IP Controller
6.52 Object_Identifier
Data Type
BACnetObjectIdentifier
Objects
Calendar, File, Binary input, Binary output, Analog input,
Analog output, Device, Scheduler
Description
This property, of the type BACnetObjectIdentifier, is a nu-
meric code that is used to identify the object. It must be
unique within the BACnet Device that maintains it. For the
device object, the object identifier must be unique internet-
work-wide.
6.53 Object_List
Date Type
BACnetARRAY[N] for BACnetObjectIdentifier
Objects
Device
Description
This read only property is a BACnetARRAY of Ob-
ject_Identifiers, one Object_Identifier for each object within
the device that is accessible through BACnet services.
6.54 Object_Name
Data Type
CharacterString
Objects
Device, Calendar, File, Binary input, Binary output, Analog
input, Analog output, Scheduler
Description
This property, of the type CharacterString, represents a
name for the object that is unique within the BACnet Device
that maintains it. The device object is unique internetwork-
wide. The minimum length of the string is one character.
The set of characters used in the Object_Name is restricted
to printable characters.