BACnet/IP Controller 750-830
•
115
Programming the PFC Using WAGO-I/O-PRO CAA
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Features
Click the link "Features" to go to a Website at which you can activate or deac-
tivate additional functions.
The "Autoreset on system error" function enables an automatic software reset
to be conducted when a system error occurs.
This function can ensure safe, reliable and continuous operation when acti-
vated for areas that are difficult to access (e.g. closed rooms, equipment cen-
ters on building roofs). An auto restart is executed as soon as the controller
has an error status that requires a restart.
With the original factory settings, this function is deactivated by default,
meaning that diagnostics is indicated via the blink code for the I/O LED when
an error occurs. A manual restart must then be conducted after error evalua-
tion and rectification.
Fig. 3-15: Web-based Management System: Features