BACnet/IP Controller 750-830 • 141
BACnet Building Controller (B-BC)
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
3.1.12.1.1.1 Data Sharing BIBBs
These BIBBs prescribe the BACnet capabilities required to interoperably per-
form the data sharing functions.
Data Sharing - ReadProperty-A (DS-RP-A)
The A device is a user of data from device B.
BACnet Service
Requests
Execute
ReadProperty x
Data Sharing-ReadProperty-B (DS-RP-B)
The B device is a provider of data to device A.
BACnet Service
Requests
Execute
ReadProperty
x
Data Sharing-ReadPropertyMultiple-A (DS-RPM-A)
The A device is a user of data from device B and requests multiple values at
one time.
BACnet Service
Requests
Execute
ReadPropertyMultiple x
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
The B device is a provider of data to device A and returns multiple values at
one time.
BACnet Service
Requests
Execute
ReadPropertyMultiple
x
Data Sharing-WriteProperty-A (DS-WP-A)
The A device sets a value in device B.
BACnet Service
Requests
Execute
WriteProperty x