310 • List of all BACnet Properties in Native Operation
Update_Interval
WAGO-I/O-SYSTEM
750
BACnet/IP Controller
6.78 Update_Interval
Data Type
Unsigned
Objects
Analog
Input
Description
This property, of the type Unsigned, indicates the maximum
period of time between updates to the Present_Value in
hundredths of a second when the input is not overridden and
not out-of-service.
6.79 UTC_Offset
Data Type
INTEGER
Objects
Device
Description
The UTC_Offset property, of the type INTEGER, indicates
the number of minutes (-780 to +780) offset between local
standard time and Universal Time Coordinated. The time
zones to the west of the zero degree meridian are positive
values, and those to the east are negative values. The value
of the UTC_Offset property is subtracted from the UTC re-
ceived in UTCTimeSynchronization service requests to cal-
culate the correct local standard time.
6.80 Vendor_Identifier
Data Type
Unsigned16
Objects
Device
Description
This property, of the type Unsigned16, is a unique vendor
identification code, assigned by ASHRAE, which is used to
distinguish proprietary extensions to the protocol.