11.2.2 Status Registers
11.2.2.1 PLC Status Register
The register 0xFA0D supplies the current status of the controller.
Possible values:
1 = PLC Stop - PLC is in STOP status.
2 = PLC Run - PLC is in RUN status
11.2.3 Electronic Nameplate
Registers 0xFA10–0xFA17 contain information from the electronic nameplate. It
is possible to read the entire nameplate or a consecutive portion of it all at once.
11.2.3.1 Order Number
The registers 0xFA10–0xFA13 contain the WAGO order number of the controller.
Example: 0750-8202/0025-0001.
0xFA10 = 0750,
0xFA11 = 8202,
0xFA12 = 0025,
0xFA13 = 0001
11.2.3.2 Firmware Version
The register 0xFA14 contains the firmware version of the controller.
11.2.3.3 Hardware Version
The register 0xFA15 contains the hardware version of the controller.
11.2.3.4 Firmware Loader/Boot Loader
The register 0xFA16 contains the firmware loader/boot loader version of the
controller.
11.2.4 MODBUS Process Image Version
The register 0xFA17 contains the MODBUS process image version of the
controller.
11.2.5 MODBUS Process Image Registers
The registers 0xFA40–0xFA45 contain size information for the process image
spaces of the controller for bit and register accesses.