388 Appendix
WAGO-I/O-SYSTEM 750
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
Table 307: Description of Configuration Scripts for “Ports and Services” – “PLC Runtime Services”
Parameters Status Call
Output/Input
Effecti
ve
General Settings
PLC runtime
version
read
get_runtime_config
running-version
Version of the enabled PLC
runtime
Possible return values:
- 0 = no runtime enabled
- 2 = CODESYS 2 enabled
- 3 =
e!
RUNTIME
enabled
Immedia
tely
write
config_runtime runtime-
version=<value>
Setting and, if necessary,
stopping of the previous runtime
version and starting of required
version
Possible entries for <value>:
- 0 = do not enable runtime
- 2 = enable CODESYS2
- 3 = enable
e!
RUNTIME
Boot project
location
read
get_runtime_config
boot-project
Memory location for a boot
project of the runtime application
Possible return values:
- HOME:// (saving on internal
memory)
- CARD:// (saving on the
memory card)
Immedia
tely
write
config_runtime boot-
project=<value>
Possible entries for <value>:
- HOME:// (saving on internal
memory)
- CARD:// (saving on the
memory card)
Default web
page
read
get_runtime_config
default-webpage
Calling web page when only
entering the IP address in the
web browser
Possible return values:
- WBM (web based
management)
- Webvisu (web visualization)
Immedia
tely
write
config_runtime default-
webpage=<value>
Possible entries for <value>:
- WBM (web based
management)
- Webvisu (web visualization)
Change
authentication
password
write
config_linux_user
user=admin new-
password=<value>
confirm-
password=<value>
Change the PLC runtime access
password
Immedia
tely