WAGO-I/O-SYSTEM 750
Commissioning 113
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
7.8.1.8.2 “Default Gateway n” Groups
You can configure two default gateways. The controller transmits all network data
not going to a station on the local network to a default gateway. First the gateway
with the lowest metric is addressed. If this is not reached, the second gateway is
used. The selection is random if the metric is the same.
A default gateway can also be configured via DHCP. These default gateways are
given the metric 10, by which they are normally used before the static gateways.
Table 51: WBM “TCP/IP Configuration” Page – “Default Gateway n” Group
Parameters
Explanation
Gateway enabled
Set here whether the selected default gateway is to
be used.
Disabled
The default gateway is not used.
Enabled
The default gateway is used.
Destination Address
Enter here if any network devices or only a specific
network device or device pool is to be accessed.
“default”
Any network devices can be reached.
Network
address
Only a specific network device or
device from the set address pool can
be reached.
Destination Mask
Enter the subnet mask of the station.
If “default” is entered at
Destination Address
, the
value “0.0.0.0” must be entered here.
Gateway Address
Enter the address of the default gateway.
Gateway Metric
Set here a number as the metric. With multiple
default gateways, the metric defines the gateway to
which data packets are first sent. Priority is given to
the gateway with the lower metric. The default value
for the metric is 20.
The lowest value is 0.
The highest value is 4.294.967.295.
Click
[Submit]
to apply the change. The change is effective immediately.