358 Appendix
WAGO-I/O-SYSTEM 750
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
750-404/000-005
The above Counter Modules have a total of 5 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 1 byte of control/ status).
The two counter values are supplied as 16 bits. The following tables illustrate the
Input and Output Process Image, which has a total of 3 words mapped into each
image. Word alignment is applied.
Table 268: Counter Modules 750-404/000-005
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
S
Status byte
1
D1
D0
Counter Value of Counter 1
2
D3
D2
Counter Value of Counter 2
Output Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
C
Control byte
1
D1
D0
Counter Setting Value of Counter 1
2
D3
D2
Counter Setting Value of Counter 2
750-638,
753-638
The above Counter Modules have a total of 6 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 2 bytes of
control/status). The two counter values are supplied as 16 bits. The following
tables illustrate the Input and Output Process Image, which has a total of 4 words
mapped into each image. Word alignment is applied.
Table 269: Counter Modules 750-638, 753-638
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
S0
Status byte von Counter 1
1
D1
D0
Counter Value von Counter 1
2
-
S1
Status byte von Counter 2
3
D3
D2
Counter Value von Counter 2
Output Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
C0
Control byte von Counter 1
1
D1
D0
Counter Setting Value von Counter 1
2
-
C1
Control byte von Counter 2
3
D3
D2
Counter Setting Value von Counter 2